18
Power Innovations
INTegral Line-Interactive Uninterruptible Power Supply
—650 VA
6—Specifications
Capacity (VA/Watt)
650 VA/406W
Model Type
Tower
Input
Nominal Voltage
100/110/115/120 VAC
Voltage
Range
Acceptable Voltage Range
85~150 VAC
Frequency
45 Hz ~ 70 Hz Auto-sensing
Boost Transfer
85/94/97.8/102 VAC ± 2%
Boost Return
90/99/102.8/107 VAC ± 2%
Buck Transfer
115/126/132/132 VAC ± 2%
Buck Return
110/121/127/127 VAC ± 2%
Low Voltage Transfer
74/81/85/89 VAC ± 2%
Low Voltage Return
79/86/90/94 VAC ± 2%
High Voltage Transfer
130/143/150/150 VAC ± 2%
High Voltage Return
125/138/145/145 VAC ± 2%
Output
Voltage
100/110/115/120 VAC
Voltage
Regulation
Line Mode
±15%
Battery Mode
< 3% RMS for entire battery voltage range
Frequency
Regulation
Line Mode
Synchronize to AC Mains
Battery Mode
60 Hz ± 0.1 Hz
Power Factor
0.625
Wave Form
Pure Sine wave
Efficiency
Line Mode
> 98%
Battery Mode
> 80%
Short-Circuit
Protection
Line Mode
Circuit Breaker
Battery Mode
Electronic Circuit
DC Start
Cold Start
Yes
Transfer Time
Typical
< 4 ms.
Battery
Battery Voltage
12VDC
Battery Type
9AH (8.5AH)
Battery Quantity
1 pce
Backup Time: 50% Load
> 6:30
Backup Time: 100% Load
>1:30
Recharging current
0.1C
Control Panel
LED display
Normal (Green)
Warning (Blinking)
Audible Alarm
Battery Mode
Beeping every 4 seconds
Low Battery
Beeping every second
UPS Fault
Beeping continuously
Overload
Beeping twice per second
Communication Interfaces
Standard
USB
Environment
Operation Temperature
0
–40 °C (32–104 °F)
Relative Humidity
0
–95% non-condensing
Audible Noise
Less than 55 dBA (at 1m)
Physical
(WxHxD) mm
115*322*130
(WxHxD) in
4 17/32 x 12 43/64 x 5 1./8
Net Weight (kgs)
6.2
Net Weight (lbs)
13 lbs 10.7 oz
NEMA Outlets (100/110/115/120 VAC)
3+1 (Option)
Safety Conformance
Safety Standard
EN62040-1-1
EMC
EN62040-2
Marks
CE
Содержание INTegral Line 650 VA
Страница 12: ...This page intentionally left blank ...