CNLT is to limit a control range and set
automatically during an auto-calibration process.
When 0% - 100% input signal is supplied, a
recognition range of the positioner is settled
according to CNLT.
If CNLT is increased as shown in Graph 3, a control
speed can become faster but a hunting problem
can happen. If CNLT is decreased as shown in Graph
4, a control speed can become slower but the
positioner works more stably.
CNTL can be adjusted by 100.
11.5.7.D [GCNL] – Gap Control Limit (default: automatically-set)
GCNL
AUTO
100-650
GCNL is to control a whole operating range. If the valve comes within
±
3% of input signal, GCNL
works with 1/2 value of CNLT for a safer control. In case that a hunting or oscillation problem
happens around the position related to the input signal, a safer control can be accomplished by
lowering GCNL.
11.5.7.E [SRPS] (default: automatically-set)
SRPS
AUTO
1BST ~ 8B
SRPS is the fast and easy setting to make the positioner work smoothly according to the working
condition of the valve.
For a stable control with an air volume booster
- Open the booster orifice by 60 – 90% before auto-calibration and set to 1BST, perform
auto-calibration again.
- Open more booster orifice in case that a hunting problem happens.
Reduce D-Gain than setting at 4N.
Standard setting
Minimalize a problem of over-shooting or under-shooting in case of the spring return type
actuator
- Automatically set in case of over-shooting or under-shooting during auto-calibration