background image

5

Power-Flo Pumps & Systems • 877-24PUMPS • www.powerflopumps.com

Installation

Pump Mounting

Arrows on the pump chamber indicate 

direction of flow through the pump. 

The pump can be mounted vertically free of 

stresses from piping system with the pump 

shaft in the horizontal position. 

NEVER install the pump with the shaft 

vertical or where the shaft falls below the 

horizontal plane.

Provide support to the pump or adjacent 

plumbing to reduce thermal and mechanical 

stress on the pump.

Installation Requirements

1. Thoroughly clean and flush the system prior 

to pump installation.

2. Do not install the pump at the lowest point 

of the system where dirt and sediment collect.

3. Ensure that water does not enter the 

terminal box during the installation.

4. (Open System) Install the pump in the 

supply line; the suction side of the pump 

should be flooded with water. Ensure that the 

static head requirement from chart is achieved.

5. If there are execessive suspended particles 

in the water, it is recommended that a strainer 

and/or filter be installed and cleaned regularly.

6. 

DO NOT START THE PUMP UNTIL THE 

SYSTEM HAS BEEN FILLED.

Start-Up

Do not use the pump to vent the system. Do 

not start the pump before filling the system. 

NEVER OPERATE THE PUMP DRY

.

Electrical:

This pump will come equipped with a 6 Ft. 

long soft jacketed 3 prong electric cord and 

strain relief connection for “outlet plug in” 

installations. The pump must be within 6 foot 

of a 115 volt receptacle.

Operating voltage and other electrical 

data can be found on the nameplate. All 

models have thermal protection and require 

no additional external protection. The 

temperature of the winding will never exceed 
allowable limits, even in locked rotor.

Operation

These circulating pumps will operate quietly 

and efficiently and provide years of service if 

sized for correct performance and installed 

properly. Under 

NO

 circumstances should the 

pump be operated without water circulation 

or without the minimum required inlet 

pressure for prolonged periods of time. This 

could result in motor and pump damage.

Failure To Operate

When the pump is first started, the shaft may 

rotate slowly until water has fully penetrated 

the bearings. If the pump does not run, the 

shaft can be rotated manually. To accomplish 

this, switch off the electrical supply and close 

the isolation valves on each side of the pump. 

Remove the indicator plug in the middle of the 

nameplate. Insert a small flat blade screwdriver 

into the end of the shaft and gently turn until 

the shaft moves freely. Replace and tighten the 

plug. Open the isolation valves and wait 2 to 

3 minutes for the system pressure to equalize 

before starting the pump.

Wet Rotor Circulator Pumps   

PFWRC66B1S

Содержание PFWRC66B1S

Страница 1: ...werflopumps com ISP No PFCirc66B1S 9 2020 OWNER S MANUAL PFWRC66B1S Wet Rotor Circulator Pumps For Indoor Use Only Maintenance Free Power Flo Pumps Systems Your Power Ful partner for all your pumping...

Страница 2: ...or certain chemical additives to the system voids the warranty Pumps build up heat and pressure during operation Allow time for pumps to cool before handling or servicing Features These Power Flo Pump...

Страница 3: ...otor Ciculator Shut Off Head ft Max Flow Gal C Cast Iron B Lead Free Bronze S Stainless Steel 1 115 V 2 230V 1P F Flanged S Copper Sweat U Union EXAMPLE PFWRC2120C1F Power FloPumps WetRotorCirculator...

Страница 4: ...t Pressure ft 5 4 5 3 psi 2 2 1 9 1 3 In a pressurized system the required inlet pressure is the minimum allowable system pressure In a system open to the atmosphere the required inlet pressure is the...

Страница 5: ...rical This pump will come equipped with a 6 Ft long soft jacketed 3 prong electric cord and strain relief connection for outlet plug in installations The pump must be within 6 foot of a 115 volt recep...

Страница 6: ...culator Pumps Figure 2 Hot Water Line Cold Water Line PFWRC66B1S Circulator Pump ONLY Hot Water Tank Remove Drain valve from Hot Water Tank insert a tee and reinstall drain valve into tee Insert a tee...

Страница 7: ...or pump is then plugged into the timer allowing for time control of the pump This unit has an internal battery backup which will in the event of loss of AC power power the unit and save maintain progr...

Страница 8: ...including but not limited to the following sand gravel cement mud tar hydrocarbons hydrocarbon derivatives oil gasoline solvents etc or other abrasive or corrosive substances wash towels or feminine...

Отзывы: