2) Control Voltage Insulation Integrity
If the user wishes to check the insulation
integrity of the control circuit, it may be
done with a 500V or 1000V insulation
tester or with and AC high potential tester.
The AC high potential test should be
made at 1125V, 60Hz, for one minute. The
charging motor must be disconnected at its
connection plug prior to testing the control
circuit. The motor itself may be similarly
tested at a voltage not to exceed 675V,
60Hz. Be sure to remove any test jumpers
and reconnect the charging motor when
the tests are complete.