Recommended Renewal Parts and Replacement Procedures
PowlVac® Electrically Operated 5kV & 15kV G&T Device
per ConEd Specification EO-2022-15 for ConEd CUSTOMER
01.4IB.50026A
g. Close the grounding switch electrically
several times to ensure that the auxiliary
switch operates smoothly.
h. Replace the upper front cover.
11) Primary Contact Spring Assembly
These springs are located at the outer end
of the primary contact stabs (Figure 2a, f).
Ensure that the control circuits are
deenergized and the ground and test device
is deenergized, disconnected by means of
a visible break, and securely grounded. Do
NOT start to work on a closed ground and test
device or a ground and test device with the
main closing spring charged.
!
CAUTION
Perform these steps to replace the primary
contact spring assembly:
a. Depress spring support sufficiently to
allow keeper to be removed.
b. Remove slotted washer, spring support,
and spring.
c. Slide new spring onto spring support
and place spring support in slot
between fingers.
d. Place slotted washer over spring
support on other side of spring from
fingers.
e. Depress head of spring support and
install keeper in end of spring support.
f. Release spring slowly, allowing keeper
to seat properly.
Note:
Springs are to be installed in every
other slot in fingers; top, center, and
bottom. The second and fourth slots
are empty.
12) Ground Shoe Finger Assembly
The ground shoe assembly is located at the
rear edge of the ground and test device
floor pan, between the center and right
Ensure that the control circuits are
deenergized and the ground and test device
is deenergized, disconnected by means of
a visible break, and securely grounded. Do
NOT start to work on a closed ground and test
device or a ground and test device with the
main closing spring charged.
!
CAUTION
Perform these steps to replace the ground
shoe finger assembly:
a. Elevate the ground ant test device so
that there is at least 6” of clear space
below the bottom pan of the device.
b. Remove the bolts holding the two
ground shoe mounting brackets to
the ground bar, and remove the two
brackets.
c. Press down on finger assembly and
remove it from the bottom of the
ground and test device.
d. Remove four socket head screws
holding two side finger assemblies to
two red spacer tubes.
e. Assemble new side finger assemblies to
red spacer tubes.
f. Wipe old lubricant off ground bars on
ground and test device and apply a thin
coat of contact lubricant B - Grease to
ground bars.
g. Insert new finger assembly from below
the floor pan and press up until the
upper lobe of the fingers snaps into
place on the ground bus.
h. Reinstall the two mounting brackets.