![Powell 27PV25ASD Скачать руководство пользователя страница 69](http://html1.mh-extra.com/html/powell/27pv25asd/27pv25asd_manual_1585523069.webp)
Powered by Safety
®
61
IB-65100
Recommended Renewal Parts and Replacement Procedures
10) Auxiliary Switch
The auxiliary switch is located on the lower
left front of the mechanism area
(Figure 6, h).
CAUTION
CAUTION
!
Ensure that the control circuits are
deenergized and the circuit breaker is
deenergized, disconnected by means of a
visible break, and securely grounded. Do NOT
start to work on a closed circuit breaker or a
circuit breaker with the main closing spring
charged.
Perform the following steps to replace the
auxiliary switch:
a. Remove the front cover of the circuit
breaker.
b. Disconnect the wires from the auxiliary
switch, being careful to note which
wires go to which terminal.
c. Remove the “E” ring securing the
switch operating arm to the operations
counter linkage.
d. Remove the two screws holding the
auxiliary switch to its mounting bracket
and remove the switch.
e. Insert the new switch and attach it to
the mounting bracket with the two
screws removed in
Step d
.
f. Insert the operating arm of the
switch into the hole at the end of the
operations counter linkage and secure it
with the “E” ring removed in
Step c.
g. Reconnect the wiring. Make sure
the wires are connected to the same
terminals from which they were
removed.
h. Operate the circuit breaker electrically
several times to ensure the switch
functions properly.
i. Replace the front cover