Servicing & Maintenance
Replacement of Thermostats
(Flowsure/F)
1. Remove the front and top covers.
2. Pull off the temperature control knob.
3. Un-clip the programmer assembly and push into the
controls assembly.
4. Remove the facia retaining screws at the base of the
facia.
5. Lift off the facia and disconnect the indicator lights
plug.
6. Disconnect the inside and rear electrical connectors.
7. Remove the controls assembly lid securing screws
and remove the lid.
Note which way the electrical connectors fit before
removing any of the thermostats.
Re-assemble in reverse order unless stated otherwise.
Boiler Control Thermostat
1. Disconnect the electrical connections.
2. Remove the clip and withdraw the sensor
from its pocket.
3. Remove the locknut securing the
thermostat spindle to the controls
assembly.
Limit Thermostat
1. Disconnect the electrical connections.
2. Remove the clip and withdraw the
temperature gauge bulb and limit
thermostat sensor from its pocket.
3. Remove the locknut securing the
thermostat to the controls assembly. On re-
assembly insert the thermostat sensor
before the temperature gauge bulb.
Pump Overrun Thermostat
1. Disconnect the electrical connections.
2. Unscrew the two screws securing the
thermostat to the controls assembly.
3. Remove the clip and withdraw the sensor
from its pocket.
Tank Limit Thermostat (F)
1. Disconnect the electrical connections.
2. Unscrew the two screws securing the
thermostat to the controls assembly.
3. Remove the clip and withdraw the sensor
from its pocket.
DHW Overheat Thermostat (Flowsure)
1. Disconnect the electrical connections.
2. Unscrew the two screws securing the
thermostat to the bracket on the pipe.
Heatstore Thermostat (F)
1. Disconnect the electrical connections.
2. Unscrew the two screws securing the
thermostat to the bracket on the pipe.
Automatic Air Vent
1. Drain the boiler using the boiler drain point
provided.
2. Unscrew the automatic air vent and fit a
new one in the reverse order.
3. Fill the system as described in Section 2-
Pre - installation Requirements.
Содержание Statesman 45/50
Страница 30: ...30 Part No 5102478 Installation Commissioning Fig 21 ...
Страница 31: ...Part No 5102478 31 Fig 22 Installation Commissioning ...
Страница 32: ...32 Part No 5102478 Installation Commissioning Fig 23 ...
Страница 35: ...Part No 5102478 35 Fig 25 Installation Commissioning ...
Страница 45: ...Part No 5102478 45 Servicing Maintenance Fig 31 ...
Страница 46: ...46 Part No 5102478 Servicing Maintenance Fig 32 ...
Страница 51: ...Part No 5102478 51 Notes Notes ...