Technical Data
Table 1
Technical Data
System
Flowsure
Model
45/50
50/70
70/90
90/110
F
Btu/h
kW
Btu/h
kW
Btu/h
kW
Btu/h
kW Btu/h
kW
Maximum Output
51,000
15
68,000
20
89,000
26
110,000
32
85,000 25
Minimum Output
44,000
13
51,000
15
68,000
20
89,000
26
68,000 20
Factory Set Output
Kerosine
51,000
15
61,000
18
82,000
24
102,000
30
82,000 24
Gas Oil
51,000
15
61,000
18
82,000
24
102,000
30
82,000 24
Riello Burner Type
RDB1
RDB1
RDB1
RDB2
RDB1
Combustion Head Type
Kerosine
LD2SH
LD2SH
LD3
LD3
LD3
Gas Oil
LD2SH
LD2SH
LD3
LD3
LD3
Nett Full Load Efficiency
%
93.2
87.5
92.6
89.8
88.0
Boiler Gas Volume
m³
0.041
0.041
0.058
0.055
0.058
Exit Flue Gas Mass Flow (Max)
kg/h
23.42
32.81
41.72
52.14
40.98
Flue Gas Temperature Rise
Above Ambient
° C
200
220
230
235
245
Resistance To Combustion
Products
mbar
0.15
0.4
0.55
0.7
0.7
Maximum Hearth Temperature
° C
60
62
50
50
65
Water Side Resistance (Cold)
10 °C Differential
mbar
11.0
11.0
21.2
18.3
15.0
20 °C Differential
mbar
4.0
4.0
6.7
1.9
6.0
Maximum Static Head
90 ft. Water (40 p.s.i.)
Minimum Static Head
5.0 ft. Water (3.0 p.s.i.)
Maximum Operating Temperature
82 °C (180 °F)
Minimum Operating Temperature
55 °C (131 °F)
Maximum Boiler Operating Pressure
3 Bar (43.5 p.s.i.) (Class 2)
Conventional Flue Draught at Boiler
Flue Outlet
0.035 "w.g. (8.75 N/m²) Minimum 0.16 "w.g. (40.0 N/m²) Maximum
Limit Thermostat Setting
110 °C (230 °F) Manual Reset
Maximum Casing Panel Temperature
Less Than 35 °C Above Room Temperature
Maximum Surface Temperatures of
Adjusting, Control & Safety Devices
Less Than 30 °C Above Room Temperature
Electrical Supply
230V 1 Phase 50Hz Fuse 5A
Model
Flowsure
F
DHW Limit Thermostat Setting
73 °C (163 °F)
DHW Store Thermostat Setting
73 °C (163 °F)
DHW Store Limit Thermostat Setting
88 °C (190 °F)
Pump Overrun Thermostat Setting
88 °C (190 °F)
88 °C (190 °F)
Flow Restrictor
13 l/m (Brown)
17.5 l/m (Green)
Maximum DHW Flow Rate
13 ± 1.5 l/m (2.9 ± 0.3 g/m)
17.5 ± 1.5 l/m (3.9 ± 0.3 g/m)
Minimum DHW Flow Rate
2.5 ± 0.5 l/m (0.5 ± 0.1 g/m)
2.5 ± 0.5 l/m (0.5 ± 0.1 g/m)
Maximum DHW Inlet Pressure
10 Bar (145 p.s.i.)
10 Bar (145 p.s.i.)
Minimum DHW Inlet Pressure
1 Bar (14.5 p.s.i.)
1 Bar (14.5 p.s.i.)
DHW Temperature Rise At a Constant
30 °C
12.5 l/m (2.7 g/m)
17.0 l/m (3.7 g/m)
50 °C
7.5 l/m (1.6 g/m)
12.0 l/m (2.6 g/m)
Store Capacity
40 Litres
Time to Achieve Storage Temperature
12 Minutes (From Cold)
Содержание Statesman 45/50
Страница 30: ...30 Part No 5102478 Installation Commissioning Fig 21 ...
Страница 31: ...Part No 5102478 31 Fig 22 Installation Commissioning ...
Страница 32: ...32 Part No 5102478 Installation Commissioning Fig 23 ...
Страница 35: ...Part No 5102478 35 Fig 25 Installation Commissioning ...
Страница 45: ...Part No 5102478 45 Servicing Maintenance Fig 31 ...
Страница 46: ...46 Part No 5102478 Servicing Maintenance Fig 32 ...
Страница 51: ...Part No 5102478 51 Notes Notes ...