6.0 System Details
11
© Baxi Heating UK Limited 2005
6.1
Water Circulating Systems
1. The boiler is suitable for use with open vent fully
pumped systems and sealed systems .
The following conditions should be observed on all
systems:
• The static head must not exceed 30m of water.
• The boiler must not be used with a direct cylinder.
• Drain cocks should be fitted to all system low points.
• All gas and water pipes and electrical wiring must be
installed in a way which would not restrict the servicing
of the boiler.
• Position isolating valves as close to circulating pump as
possible.
6.2
Treatment of Water Circulating
Systems
• All recirculatory water systems will be subject to
corrosion unless an appropriate water treatment is
applied. This means that the efficiency of the system
will deteriorate as corrosion sludge accumulates within
the system, risking damage to pump and valves, boiler
noise and circulation problems.
• When upgrading existing systems that exhibit evidence
of sludging, it is advisable to clean the system prior to
treatment in order to remove any sludge and reduce
the likelihood of these deposits damaging new
components.
• When fitting new systems flux will be evident within
the system, which can lead to damage of system
components.
• All systems must be thoroughly drained and flushed
out. Using, for example Betz-Dearborn Sentinel X300
or X400 or Fernox Superfloc Universal Cleanser. They
should be used following the flushing agent
manufacturer’s instructions.
• System additives - corrosion inhibitors and flushing
agents/descalers should be suitable for aluminium and
comply to BS7593 requirements, e.g. Betz-Dearborn
Sentinel X100 and Fernox-Copal which should be used
following the inhibitor manufacturer’s instructions.
Failure to flush and add inhibitor to the system will
invalidate the boiler warranty.
• It is important to check the inhibitor concentration
after installation, system modification and at every
service in accordance with the manufacturer’s
instructions. (Test kits are available from inhibitor
stockists.)
• For information or advice regarding any of the above
contact Technical Enquiries Tel. 08706 049 049