background image

17

INSTALLATION INSTRUCTIONS - Page 17

Figure 13 PRINCIPAL OF WIRING

WIRING
WARNING:

 This appliance must be earthed.

The boiler and all external control circuit wiring must be
supplied from the same single isolating switch and should be
fused at 3A.

Care must be taken to ensure that all wiring to the boiler is
kept clear of sharp edges and hot surfaces.

Ensure that the earth conductor is longer than the L, N, and
SWL from the point of anchorage, so that the current
carrying conductors become taut before the earth conductor,
if the cable is pulled out of the cable clamp.

The boiler terminal block which is situated in the control box
is not designed to accept wiring from all the on site controls
and therefore the installer will usually need to incorporate a
suitable junction box or Potterton Electronic Programmer.

The principle of wiring is shown in Fig 13. It should be noted
that the pump must be wired directly to the boiler terminal
block on FULLY PUMPED systems and to the junction box
or programmer on combined GRAVITY HOT
WATER/PUMPED CENTRAL HEATING systems.

Figure 14 ACCESS TO THE BOILER

ELECTRICAL TERMINAL BLOCK

Remove control box securing screw and lower the control
box to gain access to the boiler terminal block.

Figure 15 WIRING THE BOILER

FOR A FULLY PUMPED SYSTEM

Route a four core cable through the plastic bush at the rear
of the control box and the cable clamp as illustrated Fig 15,
and connect it to the boiler input terminals as follows:-

Permanent live to terminal marked MAINS ‘L’
Neutral to terminal marked MAINS ‘N’
Earth to terminal marked MAINS +
Switched live from external controls to terminal marked
MAINS SwL.

If there are no secondary controls fitted connect the SwL
terminal to permanent live in the external junction box.

Secure the cable within the cable clamp by tightening the
securing screws.

Following the pump manufacturers instructions connect the
pump supply wires to terminals marked PUMP, L, N and 4”
on the boiler terminal block.

Route the cable through the plastic bush in the rear of the
control box and cable clamp as illustrated Fig 15. Secure
cable in cable clamp by tightening the two securing screws.

Close control box and replace securing screw.

Содержание PRIMA 30C

Страница 1: ...30C 40C 50C 60C open flue gas fired boiler FOR USE WITH NATURAL GAS G20 ONLY Read these instructions thoroughly before working on the boiler Leave the instructions adjacent to the gas meter ...

Страница 2: ...al Page No 2 Installation Instructions Page No 13 Accessories Page No 3 Commissioning Page No 19 Installation Data Page No 3 Servicing Instructions Page No 21 Boiler Dimensions Page No 3 Health and Safety Information Back Page Site Requirements Page No 5 Control Systems Supplied in Technical Data Page No 7 Pipework and Wiring Guide Literature pack Users Instructions GENERAL Once the pilot has been...

Страница 3: ...ALLATION DATA Page 3 The installation of the boiler must be in accordance with the latest relevant requirements of the Gas Safety Installation and Use Regulations 1994 local building regulations IEE Wiring Regulations and the byelaws of the local Water Undertaking Detailed recommendations are contained in the following British Standard Codes of Practice BS6798 BS5440 Part 1 BS5440 Part 2 BS55449 P...

Страница 4: ...4 GENERAL ARRANGEMENT Page 4 Figure 2 GENERAL ARRANGEMENT ...

Страница 5: ...following minimum clearances must be maintained after installation for correct operation and servicing of the boiler 610mm 2ft at the front of the boiler 5mm 0 2in each side of the boiler 100mm 4in at the top 100mm 4in at the bottom where fitted above a working surface etc Additional clearances to these may be required for installation and are left to the discretion of the installer Combustion Air...

Страница 6: ...he products of combustion from the boiler The flue connecting socket on the boiler is designed to accept flue pipe to BS567 If a fluepipe to BS715 is to be used an adaptor must be fitted to the boiler connecting socket Reference should be made to The Building Regulations and British Standard 5440 Part 1 The following notes have been compiled for your guidance a The flue pipe should be at least 25m...

Страница 7: ...imum Circulating Head Gravity systems 1 2m 4ft Gas Supply Pressure 20 mbar Maximum Flow Temperature 82 C Electricity Supply 240v 50Hz fused at 3A Flow Return Connection 28mm copper Gas Supply Connection Rc in BSP Female Power Consumption 20 watts 30 40 model 50 60 model Water Content 1 8 litre 2 5 litre 0 4 gal 0 55 gal Appliance Weight installed 36 3 kg 44 0kg 80 0 lbs 97 0 lbs Appliance Weight l...

Страница 8: ...ition valves are used in the system the resistance through them quoted in their manufacturers literature must be taken into account The pump may be fitted on either the flow or return and on FULLY PUMPED systems MUST be wired directly to the boiler terminal block see Fig 14 It must be fitted with two isolating valves which are positioned as close to the pump as possible Isolation of the valves mus...

Страница 9: ...EATING SYSTEMS Where a cylinder thermostat and zone valve are fitted to control the temperature of the domestic hot water it is recommended that a by pass be installed in the gravity circuit A suggested method of doing this is shown in Fig 5 where the bathroom radiator is connected into the gravity circuit and is fitted with two lockshield valves Mechanically operated thermostatic domestic hot wat...

Страница 10: ... Water Cylinder 2 litres If the system is extended the expansion vessel may have to be increased unless previous provision has been made for the extension Where a vessel of the calculated size is not available the next available larger size should be used The boiler flow temperature is controlled at approximately 82 C The vessel size can now be determined from the following table where V System vo...

Страница 11: ...11 TECHNICAL DATA Page 11 Figure 4 OPEN VENTED FULLY PUMPED SYSTEM WITH A COMBINED FEED AND VENT Figure 5 OPEN VENTED GRAVITY DOMESTIC HOT WATER PUMPED CENTRAL HEATING ...

Страница 12: ...12 TECHNICAL DATA Page 12 Figure 6 FULLY PUMPED SEALED SYSTEM ...

Страница 13: ...ervice Cock Accessory Packs Adjustment screws Figure 7 TEMPLATE Place template in proposed boiler position taking due account of the information given previously and the position of the flue the minimum side clearances are automatically allowed for Refer to page 5 for top and bottom clearances which can be measured from the template Ensure that the template is level and mark hole positions B If th...

Страница 14: ...the boiler if not pull controls cover forward 25mm lower to release from the four side fixings and pull forward clear of the thermostat knob Remove door by undoing the two lower fixing screws and lift door off the two upper hinge brackets Engage adjustment screws into the boiler legs but do not screw in fully at this stage ...

Страница 15: ...rtical alignment with rear wall as necessary using the adjustment screws Remove the temporary cardboard packing pieces from either side of the casing Remove the four securing screws and withdraw the inner draught diverter assembly Check that the flueway baffles are correctly located and retained in the flueways as shown in Fig 10 Reassemble the draught diverter Make the flue connection to the boil...

Страница 16: ...ped return branch of the tee as illustrated in Figs 11 11B Remove gas service cock from the auxilliary pack and attach it to the union nut on the inlet to the gas assembly With the inlet connection of the gas service cock facing the rear connect the gas supply pipe Figure 11B WARNING UNDER NO CIRCUMSTANCES SHOULD A REDUCING SET BE FITTED Figure 12 NOTE The boiler is despatched with the overheat Th...

Страница 17: ...or programmer on combined GRAVITY HOT WATER PUMPED CENTRAL HEATING systems Figure 14 ACCESS TO THE BOILER ELECTRICAL TERMINAL BLOCK Remove control box securing screw and lower the control box to gain access to the boiler terminal block Figure 15 WIRING THE BOILER FOR A FULLY PUMPED SYSTEM Route a four core cable through the plastic bush at the rear of the control box and the cable clamp as illustr...

Страница 18: ...g 16 Connect the cable to the boiler input terminals as follows Switched live on the GRAVITY DHW control circuit to terminal marked MAINS SwL Neutral to terminal marked MAINS N Earth to terminal marked MAINS Secure the cable within the clamp by tightening the two securing screws The pump should be connected to PUMPED CENTRAL HEATING control circuit at the junction box See FIG 13 Figure 17 FUNCTION...

Страница 19: ...clockwise ensuring the symbol lines up with the datum mark on the gas valve body See Fig 19 This ensures that the valve is in the OFF condition G Partly depress and turn the control knob anti clockwise until the symbol lines up with the datum mark on the gas valve body Press and hold in the control knob and press the spark generator button until a click is heard Release the spark generator button ...

Страница 20: ...ss valve should be adjusted with the boiler operating under minimum load conditions to maintain sufficient water flow through the boiler to ensure that the overheat thermostat does not operate under normal operating conditions J Remove the temporary label from the front of the casing having checked compliance with the information it contains Figure 19 GAS CONTROL VALVE Figure 20 PILOT BURNER Pilot...

Страница 21: ...ential to ensure continued safe and efficient operation The frequency of cleaning will depend upon the particular installation conditions and the use to which the appliance is put but in general once per year should be adequate It is the law that all gas appliances are installed and serviced by competent persons as stated in Gas Safety Installation and Use Regulations 1994 Electrical installation ...

Страница 22: ...22 SERVICING INSTRUCTIONS Page 22 Figure 21 PREPARING THE BOILER FOR SERVICING Figure 21B Figure 21C ...

Страница 23: ...above and below the heat exchanger use a suitable brush and remove all deposits from between the fins When cleaning the front flueway protect the insulation inside the upper front panel by passing the front baffle into the flueway as illustrated in FIG 21 B 4 COMBUSTION CHAMBER INSULATION Check the combustion chamber insulation for damage If damaged replace as described under replacement 5 REASSEM...

Страница 24: ...ND DISPOSING OF A BROKEN SIGHT GLASS a Carry out operations A B C D in section 1 PREPARING BOILER FOR SERVICE b Remove three M4 nuts from sight glass retainer and remove sight glass assembly c Replacement is the reverse of removal taking care that the clear circle in the sight glass lines up with the hole in the combustion chamber door NOTE new gaskets must be used when sight glass is fitted ELECT...

Страница 25: ...e two split grommets to the new thermostat capillary carefully bend the new capillary to match the contour of the disconnected one h Ensure that the capillary is routed away from hot metallic surfaces see Fig 18a and the sensor bulb is located centrally between the two locating clips Also ensure that the location pin of the thermostat is properly located before tightening the locking nut i Make su...

Страница 26: ...26 SERVICING INSTRUCTIONS Page 26 Figure 23 FAULT FINDING CHART ...

Страница 27: ...974 378 496 9 2 6mm Burner Injector 30C boiler 410989 338 516 3 1mm Burner Injector 40C boiler 410990 338 517 3 55mm Burner Injector SOC boiler 410994 289 120 3 8mm Burner Injector 60C boiler 410993 338 520 10 Overheat Thermostat RANCO 404509 378 501 11 Boiler Thermostat RANCO K36 404510 378 550 12 Spark Generator VERNITRON 407693 382 887 13 Boiler Thermostat knob 225251 338 445 14 Flue Brush opti...

Страница 28: ...Precautions People with a history of skin complaints may be particularly susceptible to irritation High dust levels are only likely to arise following harsh abrasion In general normal handling and use will not present discomfort follow good hygiene practices wash hands before consuming food drinking or using the toilet First Aid Medical attention must be sought following eye contact or prolonged r...

Отзывы: