Important!
The respective regulations and standards of the screed manufacturer
have to be observed.
A correct function is only possible with a correctly installed heating system (hy-
draulic, electrical systems and settings).
Deviations can only lead to damage of the screed.
The floor curing function can be stopped prematurely by setting
0=OFF
.
Floor curing setp manually
(851, 1151, 1451)
Setting of temperature, up to which manual control is carried out at activated
floor curing function (see prog. no. 850).
Floor curing setp current
(855, 1155, 1455)
Display of the current floor curing setpoint.
Screed day actual
(856, 1156, 1456)
Display of the current day of the floor curing function.
Excess heat draw
(861, 1161, 1461)
If the excess temperature draw is activated via input H1 to H5 or a maximum
temperature is exceeded in the system, this excess heat energy can be released
by a heat draw of the room heating.
-
Off
: the function is switched off.
-
Heating mode
: the function is limited to only a draw during the heating time.
-
Always
: the function is generally released.
With buffer
(870, 1170, 1470)
This parameter establishes whether the heating circuit can be supplied by a buf-
fer or only from a heat generator. The function has the effect of whether with a
heat demand the system pump goes into operation.
-
No
: the heating circuit is supplied from the boiler.
-
Yes
: the heating circuit can be supplied from the buffer.
With primary controller/sys-
tem pump
(872, 1172, 1472, 5092)
This parameter establishes whether a zone system pump goes into operation
with a heat demand of the heating circuit. This system pump is based on the seg-
ment, in which this controller is located (LPB bus system) and which is controlled
with a primary control.
-
No
: the heating circuit will be fed without primary control unit/feed pump.
-
Yes
: the heating circuit is supplied after the primary control with the system
pump.
Pump speed reduction
(880, 1180, 1480)
Speed reduction of the heating circuit pump can be done acc. to operating level or
acc. to pump characteristic curve.
Operating level
: With this option the speed of the heating circuit pump is calcula-
ted acc. to the operating level. The pump is controlled in operating level comfort
(incl. optimization) or during active floor curing function with parameterized
maximum speed. With reduced operating level the pump is controlled with the
parameterized minimum speed.
Characteristic
: The pump speed of the heating circuit pump is calculated based on
the actually held flow temperature and the current flow set point. The common
flow temp setpoint is used for the actual value If no common flow temperature
sensor is available the boiler flow actual value is used. The temperature actual
value is attenuated with a filter (time constant capable of parameterization)
Pump speed min
(882, 1182, 1482)
Using this function the minimum speed for the heating circuit pump can be
specified.
Programming
7308272-03 03.14
Paramount three 30-115 kW
87
Содержание Paramount 40
Страница 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Страница 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Страница 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Страница 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...