Function
Prog.
no.
Level
1)
Standard value
With prim contr/system pump
No | Yes
1930
E
Yes
Swimming pool circuit
Flow temp setp cons request
1959
C
70°C
DHW charging priority
No |Yes
1974
E
Yes
Excess heat draw
Off | On
1975
E
ON
With buffer
No |Yes
1978
E
Yes
With prim contr/system pump
No |Yes
1980
E
Yes
Swimming pool
Setpoint solar heating
2055
Eu
26°C
Setpoint source heating
2056
Eu
22°C
Charging priority solar
Priority 1 | Priority 2 | Priority 3
2065
E
Priority 3:
Swimming pool temp max
2070
E
32°C
With solar integration
No | Yes
2080
E
Yes
Primary contr/system pump
Flow temp setpoint min
2110
E
8°C
Flow temp setpoint max
2111
E
80°C
Syst pump on heat gen lock
Off | On
2121
E
Off
Mixing valve boost
2130
E
0°C
Actuator running time
2134
E
120 s
Boiler
Release below outside temp
2203
E
--- °C
Full charging buffer
Off | On
2208
E
Off
Setpoint min
2210
E
20°C
Setpoint max
2212
E
88°C
Setpoint manual control
2214
Eu
60°C
Burner running time min
2241
E
1 min.
Burner off time min
2243
E
7 min.
SD burner off time
2245
E
20°C
Pump overrun time
2250
E
2 min.
Pump overr time after DHW
2253
E
1 min.
Frost prot plant boiler pump
Off | On
2300
E
Off
Boiler pump on heat gen lock
Off | On
2301
E
Off
Impact heat generation lock
Heating mode only | Heating and DHW mode
2305
E
Heating mode only
Programming
7308272-03 03.14
Paramount three 30-115 kW
59
Содержание Paramount 40
Страница 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Страница 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Страница 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Страница 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...