INSTALLATION REQUIREMENTS – Page 7
Note
: Where a flue terminal is installed less than one
metre from a plastic, or painted gutter, or 500mm from
painted eaves, an aluminium shield one metre long,
should be fitted to the underside of the gutter or painted
surface. A suitable wall plate should be fitted to the
painted wall surface of a mobile home.
IMPORTANT:
It is absolutely ESSENTIAL to ensure that
products of combustion discharging from the terminal
cannot re-enter the building, or any other adjacent
building, through ventilators, windows, doors, natural air
infiltration, or forced ventilation/air conditioning. If
products of combustion are found to be re-entering any
building, the appliance MUST be turned OFF
IMMEDIATELY.
FIG. 3 FLUE TERMINAL POSITIONS
Mm. Distance mm
A
DIRECTLY BELOW AN OPENABLE WINDOW, AIR VENT, OR ANY
OTHER VENTILATION OPENING
300
B
BELOW GUTTER, DRAIN/SOIL PIPE
75
C
BELOW EAVES (HORIZONTAL FLUE ONLY)
200
*
BELOW A BALCONY/CARPORT ROOF
NOT RECOMMENDED
E
FROM VERTICAL DRAIN PIPES AND SOIL PIPES
75
F
FROM INTERNAL OR EXTERNAL CORNERS
300
G
ABOVE ADJACENT GROUND OR BALCONY LEVEL
300
H
FROM A SURFACE FACING THE TERMINAL
600
I
FACING TERMINALS
1200
*
FROM OPENING (DOOR/WINDOW) IN CARPORT INTO DWELLING
NOT RECOMMENDED
K
VERTICALLY FROM A TERMINAL ON THE SAME WALL
1,500
L
HORIZONALLY FROM A TERMINAL ON THE SAME WALL
300
M
ADJACENT TO OPENING
300
N
ABOVE ROOF LEVEL (TO BASE OF TERMINAL)
300
P
FROM ADJACENT WALL TO FLUE
300
Q
FROM INTERNAL CORNER TO FLUE
400
*
BELOW EAVES OR BALCONY (VERTICAL FLUE)
NOT RECOMMENDED
S
FROM FACING TERMINAL
2000
Содержание envoy 30
Страница 4: ...4 TECHNICAL DATA PAGE 4 FIG 2 GENERAL ARRANGEMENT ...
Страница 28: ...28 FAULT FINDING CHART 1 Page 28 ...
Страница 29: ...29 FAULT FINDING CHART 2 Page 29 ...
Страница 30: ...30 BOILER INTERNAL WIRING Page 30 ...
Страница 31: ...31 BOILER WIRING LAYOUT Page 31 ...
Страница 36: ...36 Back Page ...