PSN-1000 POWER EXPANDER-5403599-REV C-04/17
10
- NAC 1 + - NAC 5 + - NAC 3 +
-
+ A
- NAC 2 + - NAC 4 + - NAC 6 +
-
+ A
P-LINK
Releasing
Device
End of line device
5.1k ohm 1/2W
Part #3005012
Note:
EOL Device shall be installed in the same
electrical enclosure as the releasing device.
Figure 9
Municipal Box Connection
When programmed as a municipal box connection, the circuit is power limited, is supervised for open and short
circuit conditions and provides a local energy connection.
Trip current = NAC1-NAC6 = 3 Amps
Max Voltage = 24 VDC
The panel has ground fault detection on municipal box connection circuits. The impedance to ground for ground
fault detection is 0 ohms.
Figure 10
- NAC 1 + - NAC 5 + - NAC 3 +
-
+ A B
- NAC 2 + - NAC 4 + - NAC 6 +
-
+ A B
P-LINK
Notes:
The EOL device shall be installed in the same electrical
enclosure as the Municipal Box.
Municipal
Box
+
-
End of line device
5.1k ohm 1/2W
Part #3005012