![Potter PSN 1000(E) Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/potter/psn-1000-e/psn-1000-e_installation-manual_1582935015.webp)
PSN-1000 POWER EXPANDER-5403599-REV C-04/17
15
SLC#____ Current Draw Worksheet (Repeat for each SLCE-127 being powered by the PSN-1000)
Description
Qty
Standby
(mA)
Total
Standby (mA)
Alarm
(mA)
Total
Alarm (mA)
SLCE-127 Main Board
1
60
60
60
60
Analog photo smoke detector (PSA)
0.325
0.325
Analog photo DUCT smoke detector (DSA)
0.325
0.325
Analog photo smoke / fixed heat detector (PSHA)
0.325
0.325
Analog fixed heat detector (FHA)
0.325
0.325
Analog combo heat detector (RHA)
0.325
0.325
Conventional initiating zone module - 4 inch mount (CIZM-4) *Note 1
0.325
1.0
Miniature contact module (MCM)
0.325
0.325
Single contact module - 4 inch mount (SCM-4)
0.325
1.0
Dual contact module - 4 inch mount (DCM-4)
0.325
1.0
Monitored output module - 4 inch mount (MOM-4) *Note 2
0.325
1.0
Twin relay module - 4 inch mount (TRM-4)
0.325
1.0
Short circuit isolator (SCI) *Note 3
0.325
2.34
Analog sounder base (ASB)
0.325
0.325
Analog relay base (ARB)
0.325
0.325
Isolator base (AIB) *Note 3
0.325
2.34
SLC alarm LED Current
n/a
n/a
n/a
27.0
SLC Standby
Current
SLC Alarm
Current
* Note 1: CIZM requires 24VDC power source. Standby current Style D = 4.90 ma, Style B (8.5 ma). Alarm Current = 50.0 ma
* Note 2: MOM requires 24VDC power source. Standby current = 1.6 ma. Alarm Current = 1.60 ma
* Note 3: In Class B (Style 4) installations the following rule must be observed:
Number of SLC Devices
+ Number of Isolated branches * 8
Must be <= 127
* Note 4: In Class A (Style 7) installations the following rule must be observed:
Number of SLC Devices
+ Number of Isolators used
Must be <= 127