MFG. #5401162 - REV C-1

12/10

PRINTED IN USA

 PAGE 3 OF 8

MODEL PS10 (VDS)

PRESSURE SWITCH

POSITIVE DC

OR HOT AC

BELL

NEGATIVE DC

OR NEUTRAL AC

     LINE

     LOAD

Local Bell For Waterflow Connection

Break out thin section of divider to provide path for wires when wiring both 

switches from one conduit entrance.

One Conduit Wiring

Fig. 6

Fig. 7

Fig. 9

Removing Knockouts

W/ PRESSURE APPLIED

W/O PRESSURE APPLIED

C

C                       1                        2

C

C                       1                        2

Switch Operation

Fig. 8

•  Installation must be performed by qualified personnel and in accordance with all   

   national and local codes and ordinances.

•  Shock hazard.  Disconnect power source before servicing.  Serious injury or death  

   could result.

•  Read all instructions carefully and understand them before starting installation.  Save  

   instructions for future use.  Failure to read and understand instructions could result   

   in improper operation of device resulting in serious injury or death. 

 

•  Risk of explosion.  Not for use is hazardous locations.  Serious injury or death could result.

•  Do not tighten by grasping the switch enclosure.  Use wrenching flats on the   

   bushing only.  Failure to install properly could damage the switch and cause  

   improper operation resulting in damage to equipment and property. 

 

•  To seal threads, apply Teflon tape to male threads only.  Using joint compounds or  

   cement can obstruct the pressure port inlet and result in improper device operation  

   and damage to equipment. 

 

 

 

 

•  Do not over tighten the device, standard piping practices apply.

Terminal

C: Common

1:  Closed when installed under  

     normal system pressure.

2:  Open when installed under  

     normal system pressure.  Closes  

     on pressure drop.  Use for low  

     pressure supervision.

Terminal

1:  Open with no pressure supplied.   

     Closes upon detection of  

     pressure.  Use for waterflow  

     indication. 

2:  Closed with no pressure applied.

Содержание PS10 Series

Страница 1: ...al 0 13 BAR 2 PSI typical Maximum System Pressure 17 2 BAR 250 PSI Switch Contacts SPDT Form C 10 1 Amps at 125 250VAC 2 0 Amps at 30VDC One SPDT in PS10 1 Two SPDT in PS10 2 Environmental Specifications NEMA 4 IP66 Rated Enclosure indoor or outdoor when used with NEMA 4 conduit fittings Temperature range 40 C to 60 C 40 140 F PotterElectricSignalCompany St Louis MO CustomerService 866 572 3005 Te...

Страница 2: ...TER BY PASS VALVE WET SYSTEM WITHOUT EXCESS PRESSURE WATER MOTOR GONG WET SYSTEM ALARM CHECK VALVE OS Y VALVE RBVS WATER BY PASS VALVE RETARD PS10 DRY SYSTEM ALARM CHECK VALVE OS Y VALVE WATER BY PASS VALVE CHECK VALVE RBVS DRY SYSTEM PS10 WATER MOTOR GONG DWG 923 2AA Fig 2 Fig 4 Fig 5 Fig 3 NOTE To prevent leakage apply Teflon tape sealant to male threads only ADJUSTMENT KNOB 2 87 72 97 4 22 107 ...

Страница 3: ...nderstand instructions could result in improper operation of device resulting in serious injury or death Risk of explosion Not for use is hazardous locations Serious injury or death could result Do not tighten by grasping the switch enclosure Use wrenching flats on the bushing only Failure to install properly could damage the switch and cause improper operation resulting in damage to equipment and...

Страница 4: ...l be factory adjusted Ordering Information Model Description Stock No PS10 1 Pressure switch with one set SPDT contacts 1320011 PS10 2 Pressure switch with two sets SPDT contacts 1320021 Hex Key 5250062 Cover Tamper Switch Kit 0090200 to operate on a pressure increase of 0 27 0 55 BAR 4 8 PSI Pressure switch shall have one or two form C contacts switch contact rating 10 1 Amps at 125 250 VAC 2 0 A...

Страница 5: ...wei SPDT beim PS10 2 Umgebungsspezifikationen NEMA 4 IP66 klassifiziertes Gehäuse Innen oder Außeneinsatz mit gemäß NEMA 4 klassifiziertem Rohrleitungszubehör Temperaturbereich 40 C bis 60 C 40 bis 140 F Potter Electric Signal Company St Louis MO Customer Service 866 572 3005 Tech Support 866 956 0988 Canada 888 882 1833 www pottersignal com integriertundelektrischmitderSteuereinheitverbunden dief...

Страница 6: ... VENTIL NASSAN LAGE ALARM VENTIL NASSAN LAGE ALARM VENTIL TROCKEN ANLAGE OS Y VENTIL BEIPASS VENTIL WASSER DURCHFLUSS BEIPASS VENTIL WASSER DURCHFLUSS OS Y VENTIL BEIPASS VENTIL WASSER DURCHFLUSS OS Y VENTIL NASSANLAGE OHNE ÜBERDRUCK RBVS VERZÖGERUNG PS10 RÜCK SCHLAG VENTIL RBVS TROCKENANLAGE PS10 DWG 923 2AA WASSERTURBINE MIT GONG HINWEIS Bringen Sie an den Außengewinden Teflonband an um Leckagen...

Страница 7: ...d Bestimmungen durchgeführt werden Es besteht Stromschlaggefahr Schalten Sie vor Wartungsarbeiten die Stromversorgung ab Anderenfalls könnten Sie schwer verletzt oder getötet werden Lesen Sie vor Beginn der Installation alle Anweisungen sorgfältig durch Bewahren Sie die Anweisungen zur künftigen Verwendung auf Das Nichtlesen und beachten der Anweisungen könnte zum fehlerhaften Betrieb des Geräts f...

Страница 8: ...ckschalter hat einen oder zwei Form C Kontakte Die Bestellinformationen Modell Beschreibung Produktnr PS10 1 Druckschalter mit einem Satz SPDT Kontakte 1320011 PS10 2 Druckschalter mit zwei Sätzen SPDT Kontakte 1320021 Inbusschlüssel 5250062 Manipulationsschalter für Abdeckung 0090200 Techniker Architektenspezifikationen Druckschalter Für Wasserdurchfluss Schalterkontakte sind auf 10 1 A bei 125 2...

Страница 9: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information AMSECO PS 10 EX ...

Отзывы: