INSTALLATION MANUAL:  PAD100-DUCTR ANALOG ADDRESSABLE DUCT DETECTOR

Document 5406321-A  05/16

Potter Electric Signal Company, LLC           •           St. Louis, MO             •           Phone: (800) 325-3936               •            www.pottersignal.com

 

PAGE 2 OF 5

The examples shown below illustrate a PAD device's dip switch settings: the 1st example shows a device 

not addressed 

where all 

dip switch settings are in the 

default

 

"Off" position

, the 2nd illustrates an 

addressed PAD device

 via the dip switch settings.

Figure 2. Examples of PAD Device Showing Default Dip Switch Setting (Unaddressed) & Addressed PAD Device

Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the SLC or device.

• 

Power to the SLC is removed.

• 

Field wiring on module is correctly installed.

• 

Field wiring has no open or short circuits.

3.  Technical Specifications

Duct Detector Model #

PAD100-DUCTR

Operating Voltage

24.0V

Current Draw

500μA

Detector Head Model

PAD100-DD

Detector Head Type

Photoelectric

Sensitivity Test Method

Self diagnostic test

Air Velocity

100 to 4000 ft./min.

Ambient Temperature

32

̊ 

to 120

̊ 

F (0

̊ 

to 49

̊ 

C)

Humidity

10% to 85% Relative humidity (non-condensing)

Housing Material

Plastic backbox, clear plastic cover

Finish

Gray backbox with clear cover

Dimensions

13 1/2" L x 4 1/2" W x 2 1/4" D

Maximum Net Weight

2 lbs.

Relay Contact Rating

8A@30VDC, 10A@120VAC, 10A@250VAC

Sampling Tubes

2.5 ft., 5 ft., or 10 ft.

Sampling Tube Part Numbers 

2.5' = 1000274, 5' = 1000275, 10' = 1000276

4.  Wiring Diagrams

The wiring diagrams shown below illustrate how to wire PAD100-DRTS, MS-RA and MS-KA/P/R devices.

Figure 3. 

Example of Wiring a PAD100-DRTS

Off

On

1 2 4

16

8

32 64

All dip switches are 

shown in the "Off" 

position.

Off

On

1 2 4

16

8

32 64

Example shows this PAD device's 

address = 42. Dip switches #2, 8 & 

32 are in the "On" position.

TO ADDRESSABLE 

PAD100-DUCTR

DUCT DETECTOR

firealarmresources.com

Содержание PAD100-DUCTR

Страница 1: ...Sampling tubes are supplied in three standard lengths 2 5 ft 5 ft and 10 ft and cut to size to fit the duct Mounting the duct smoke unit is accomplished by the use of a template and 2 sheet metal screws which are provided Mounting can be achieved without the removal of the clear cover which is secured by 4 capture screws 2 Setting the Address All PAD protocol detectors and modules require an addre...

Страница 2: ...uct Detector Model PAD100 DUCTR Operating Voltage 24 0V Current Draw 500μA Detector Head Model PAD100 DD Detector Head Type Photoelectric Sensitivity Test Method Self diagnostic test Air Velocity 100 to 4000 ft min Ambient Temperature 32 to 120 F 0 to 49 C Humidity 10 to 85 Relative humidity non condensing Housing Material Plastic backbox clear plastic cover Finish Gray backbox with clear cover Di...

Страница 3: ...ircuit 1 4 inch 24VDC FROM FACP OR PREVIOUS MODULE FORM C RELAY 10A 250VAC TO NEXT MODULE FROM FACP OR PREVIOUS MODULE Note Jumper must be in Off position when using the MS KA P R 24VDC TO FACP OR NEXT MODULE TO MS RA RED WIRE TO MS RA BLACK WIRE SUPERVISION OPTION SHOWN IN OFF POSITION FORM C RELAY 10A 250VAC TO NEXT MODULE FROM FACP OR PREVIOUS MODULE PAD100 DRTS SUPERVISION OPTION TO PAD100 DRT...

Страница 4: ...e duct detector should not be mounted in areas of extreme high or low temperatures in areas where high humidity exists or in areas where the duct may contain gases or excessive dust SAMPLING TUBE ASSEMBLY The PAD100 DUCTR duct smoke detectors employ a specially notched sampling tube which may be ordered separately in one of four 4 standard lengths STN 1 0 For duct widths of 6 TO 1 0 STN 2 5 For du...

Страница 5: ...nds Note When a panel is configured to not flash LEDs the LEDs on the detectors will not flash at any time 7 Functional Testing Note Be sure to dis engage all alarm signal services releasing devices and extinguishing systems prior to performing the following test except automatic testing by the FACP Be sure to re engage these systems when all testing is complete 8 Walk Test The FACP must be placed...

Отзывы: