INSTALLATION MANUAL: PAD100-DUCTR ANALOG ADDRESSABLE DUCT DETECTOR
Document 5406321-A 05/16
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: (800) 325-3936 • www.pottersignal.com
PAGE 3 OF 5
Figure 4. Example of Wiring a PAD100-DRTS
Figure 5.
Example of Wiring a MS-RA
Figure 6.
Example of Wiring a MS-KA/P/R
Notes:
•
SLC wiring style supports the Class A, Class X and Class B.
•
SLC loop wiring and Aux PWR wiring are power limited and supervised.
•
All wiring is between #12 (max.) and #22 (min.).
•
Wire Preparation – Strip all wires 1/4 inch from their edges as shown here:
– Stripping too much insulation may cause a ground fault.
– Stripping too little may cause a poor connection and subsequently an open circuit.
1/4 inch
24VDC FROM FACP OR
PREVIOUS MODULE
FORM C RELAY
10A, 250VAC
TO NEXT MODULE
FROM FACP OR
PREVIOUS MODULE
Note: Jumper must be
in “Off” position when
using the MS-KA/P/R.
24VDC TO FACP OR
NEXT MODULE
TO MS-RA (RED WIRE)
TO MS-RA (BLACK WIRE)
SUPERVISION OPTION
SHOWN IN “OFF” POSITION
FORM C RELAY
10A, 250VAC
TO NEXT MODULE
FROM FACP OR
PREVIOUS MODULE
PAD100-DRTS
SUPERVISION OPTION
TO PAD100-DRTS
Note: Keep jumper in
“On” position when
using the PAD100-DRTS
for full wiring supervision.
24VDC FROM FACP OR
PREVIOUS MODULE
24VDC TO FACP OR
NEXT MODULE
24VDC FROM FACP OR
PREVIOUS MODULE
FORM C RELAY
10A, 250VAC
TO NEXT MODULE
FROM FACP OR
PREVIOUS MODULE
Note: Jumper must be
in “Off” position when
using the MS-KA/P/R.
24VDC TO FACP OR
NEXT MODULE
RED
RED
BLACK
KEY SWITCH
MS-KA/P/R
ALARM LED
PILOT LED
BLACK
BLACK
BLACK
SUPERVISION OPTION
SHOWN IN “OFF” POSITION
firealarmresources.com