Figure 3.
EVD-R REMOTE PICKUP DETAILS
EVD-R TERMINAL CONNECTIONS
TERMINAL TERMINAL
DESCRIPTION
NO.
NAME
1
SHIELD
Input Shield Connection from OUT SHIELD of Previous
Pickup or End of Line Resistor (See note 1)
2
SIGNAL
Input Sensor Signal from OUT SIGNAL of Previous Pickup
or End of Line Resistor (See note 1)
3
REF
Input Reference from OUT REF of Previous Pickup or End of
Line Resistor (See note 1)
4
NC
Normally Closed Connection to Safe Contact (See notes 2,3)
5
COM
Common connection to Safe Contact (See notes 2,3)
6
NO
Normally Open Connection to Safe Contact (See notes 2,4)
7
TAMPER
Tamper Connection to Safe Contact (See notes 2,5)
8
TAMPER
Tamper Connection to Safe Contact (See notes 2,5)
9
SPARE
Spare Terminal Block Connection
10
SHIELD
Output Shield Connection to IN SHIELD of Next Pickup or
EVD-M SHIELD Connection
11
SIGNAL
Output Sensor Signal to IN SIGNAL of Next Pickup or EVD-M
SIGNAL Connection
12
REF
Output Reference to IN REF of Next Pickup or EVD-M REF
Connection
NOTES:
1. Remove all factory installed 10K Ohm, 1% end of line resistors from pins 1-2 and pins
2-3 of all EVD-R's except the LAST EVD-R remote pickup in the remote pickup
network. See Figures 2b and 4 for details.
2. Connections to optional dry contacts from any UL listed safe contact. See Figure 4 for
details.
3. If a safe contact is connected, remove the factory installed jumper from pins 4-5. Pins
4-5 must be NORMALLY CLOSED for the non-alarm state.
4. Pins 5-6 must be NORMALLY OPEN for the non-alarm state.
5. If safe contact tamper is connected, remove the factory installed jumper from pins 7-8.
Pins 7-8 must be NORMALLY CLOSED for the non-tamper state.
6. Pins 1-12 are power limited.