15
EVD-2 • 5401042 • REV L • 03/05
SENSITIVITY ADJUSTMENTS
1.
Adjust the EVD-M’s internal pickup sensitivity control, RV1, to 1/2 scale (12 o’clock
position). Refer to Figure 1 for adjustment location.
2.
If remote pickups are installed, adjust the EVD-M’s remote pickup network
sensitivity control, RV2, to the minimum setting listed in Table 2. If no EVD-R’s are
installed, adjust RV2 to the minimum setting, fully counter-clockwise. Refer to
Figure 1 for adjustment location.
Table 2.
s
p
u
k
c
i
P
e
t
o
m
e
R
f
o
r
e
b
m
u
N
1
2
3
4
5
6
7
8
9
0
1
1
1
2
1
3
1
4
1
5
1
k
r
o
w
t
e
N
e
t
o
m
e
R
m
u
m
i
n
i
M
g
n
i
t
t
e
S
y
t
i
v
i
t
i
s
n
e
S
0
0
0
4
/
1
4
/
1
4
/
1
4
/
1
4
/
1
2
/
1
2
/
1
2
/
1
2
/
1
2
/
1
4
/
3
4
/
3
3.
Adjust accumulator rotary switch, S1, to desired setting. A setting of zero disables
the accumulator function. Refer to Figure 1 for adjustment location.
4.
Perform simulated attack tests on all accessible surfaces that are protected by the
EVD-M and EVD-R’s. Strike the protected surfaces using a plastic mallet or the
plastic handle of a large screwdriver. An alarm condition (as indicated by the
status LED turning RED) must occur. Lightly scrape the blade of a screwdriver
next to the EVD-M and each EVD-R. After 15 seconds of continuous scraping,
an alarm condition (as indicated by the status LED turning RED) must occur. Be
sure the scraping generates a test point voltage greater than the
minimum constant noise level shown in Table 3. Adjust sensitivity settings
to the minimum needed to achieve desired level of response.
NOTE: Extreme care should be exercised so that the protected surfaces
are not marred or damaged while performing simulated attack tests.
A voltmeter can be connected to the analog test point and pin 2 of the field wiring
terminal block to aid the installer in adjusting the sensitivity controls. Refer to
Figure 1 for analog test point location.
Table 3.
ANALOG TEST POINT LEVELS
n
o
i
t
p
i
r
c
s
e
D
l
a
n
g
i
S
l
e
v
e
L
t
n
i
o
P
t
s
e
T
g
o
l
a
n
A
l
e
v
e
L
e
s
i
o
N
t
n
e
i
b
m
A
m
u
m
i
x
a
M
C
D
V
0
2
.
0
m
u
m
i
n
i
M
t
n
a
t
s
n
o
C
m
r
a
l
A
r
o
f
e
s
i
o
N
)
g
n
il
l
i
r
D
t
p
e
c
x
e
(
)
n
o
i
t
a
r
u
d
.
c
e
s
5
1
.
n
i
m
(
C
D
V
5
2
.
0
m
u
m
i
n
i
M
e
l
g
n
i
S
m
r
a
l
A
r
o
f
e
s
i
o
N
)
n
O
r
o
t
a
l
u
m
u
c
c
A
(
C
D
V
0
7
.
0
m
u
m
i
n
i
M
e
l
g
n
i
S
m
r
a
l
A
r
o
f
e
s
i
o
N
)
f
f
O
r
o
t
a
l
u
m
u
c
c
A
(
C
D
V
5
2
.
1
5.
With the system operating in a non-alarm state, verify the operation of all tampers.
A tamper condition is indicated by the status LED turning AMBER. If the system
is in alarm when a tamper condition occurs, the status LED will remain
RED, identifying the alarm condition. The tamper alarm remote annuncia-
tor and the tamper alarm contact always identify a tamper condition.