Figure 8   Typical Wall Protection Installation

CIRCULAR AREA OF 
100% COVERAGE

RECTANGULAR AREA OF 
100% COVERAGE

DETECTOR 

RANGE

DETECTOR 

SPACING

DETECTOR 

SPACING

Table 7  Recommended Maximum EVD-1 Spacing for Wall Protection

Material

Sensitivity 
Setting

Detector 
Range

Rectangular Area of 100% Coverage

Steel plates at least 
1/4" thick

Minimum

8.0'

11.3' x 11.3'

8' x 13.9'

10' x 12.5'

15' x 5.6'

-

Half

15.0'

21.2' x 21.2'

8' x 28.9'

10' x 28.3'

15' x 26'

20' x 22.4'

Maximum

20.0'

28.3' x 28.3'

8' x 39.2'

10' x 38.7'

15' x 37.1'

20' x 34.6'

Monolithic concrete 
at least 6" thick

Minimum

16.0'

22.6' x 22.6'

8' x 31.0'

10' x 30.4'

15' x 28.3'

20' x 25.0'

Concrete block at 
least 6" thick

Minimum

16.0'

22.6' x 22.6'

8' x 31.0'

10' x 30.4'

15' x 28.3'

20' x 25.0'

All dimensions in inches

Figure 9    Dimensions

Figure 10   EVD-1 Mounting Template

All dimensions in inches

Содержание 2020230

Страница 1: ...troller RTA optional Manual 5401043 Rev N 6 09 EVD 1 Electronic Vibration Detector System Installation Operation and Instruction Manual All specifications subject to revision DWG 516 933 4900 dwgdistribution com ...

Страница 2: ... determines that said product is not operating properly as a result of causes other than defective manufacture labeling or packaging The Aforesaid Warranty Is Expressly Made In Lieu Of Any Other Warranties Expressed Or Implied It Being Understood That All Such Other Warranties Expressed Or Implied Including The Warranties Of Merchantability And Fitness For Particular Purpose Are Hereby Expressly E...

Страница 3: ...m Zone 9 EVD Wiring with Safe Detector Zone Only 10 Sensitivity Adjustments 11 Analog Test Point Levels 11 Testing 11 Safe Construction Requirements 11 Recommended Detector Locations 12 Determining the Number of Detectors for a Safe Application 12 Determining the Maximum Linear Distance on a Safe 13 Typical Safe Exterior Dimensions and Maximum Linear Distances 13 Typical UL Complete Safe Installat...

Страница 4: ...4 EVD 1 5401043 REV M 9 07 ...

Страница 5: ...0cm D Weight 0 64 lbs 0 29 kg Enclosure Base Die cast aluminum Cover Stamped Steel 22 Gauge Power Input 9 0 VDC to 16 0 VDC 12 VDC Nominal Maximum 0 1 V ripple Typical Current Supply Voltage 12 0 VDC Normal Standby Condition 26 mA Alarm Condition 24 mA Tamper Condition 34 mA With model RTA connected add 10 mA in Tamper Condition and 10 mA in Alarm condition Maximum Current Supply Voltage 16 0 VDC ...

Страница 6: ...g of the installation The EVD 1 contains a multi color LED to indicate system status This status LED indicates three states Notes 1 If both an alarm condition and a tamper alarm condition exist the status LED will indicate RED for the alarm The remote annunciators and the alarm and tamper alarm contacts will indicate both alarm and tamper alarm conditions 2 If the microprocessor fails the status L...

Страница 7: ...ing should be as specified in Table 1 or with UL listed equivalents 1 Cable clamp knockout locations are shaded Be sure to remove clamp from base and to cleanly knock out cable openings in the cable clamp before feeding wire through the clamp 2 Connections to UL listed control unit via UL listed high security cable See Table 1 See Figure 3b 3c for 4 or 6 wire installation wiring 3 Connections to r...

Страница 8: ...wiring 6 High Security B cable and connections to 24 hour alarm zone as shown are ULrequirements for UL Safe Complete installations SAFE DETECTOR ZONE 24 HOUR ALARM ZONE DRAIN WIRE FOR OUTER SHIELD DRAIN WIRE FOR INNER SHIELD HIGH SECURITY CABLE BLACK RED 12 VOLT DC SUPPLY MODEL EVD 1 CONTROL UNIT END OF LINE RESISTORS MODEL RTA RED ALARM LED YELLOW TAMPER LED TEST SWITCH CURRENT LIMITING RESISTOR...

Страница 9: ...9 EVD 1 5401043 REV M 9 07 Recommended Control Panel Wiring With Safe Detector Zone And 24 Hour Alarm High Security B Cable Required For UL Safe Complete Installations Figure 3b DWG 1043 10 ...

Страница 10: ...10 EVD 1 5401043 REV M 9 07 Optional Control Panel Wiring With Safe Detector Zone Only 4 Conductor Shielded Cable Required Figure 3c ...

Страница 11: ... by the status LED turning AMBER If the system is in alarm when a tamper condition occurs the status LED will remain RED identifying the alarm condition The tamper alarm remote annunciator and the tamper alarm contact always identify a tamper condition Testing Applying a magnet to the side of the EVD 1 controller see Figure 1 actuates a magnetic switch and generates a test signal The EVD 1 activat...

Страница 12: ...d detector location s of a safe application with double doors Multiple Detector Applications When more than two detectors are required on a safe mount the first two detectors as recommended for a two detector application Mount the remaining detectors on the remaining surfaces centered and spaced evenly to ensure complete detector coverage Alternately mount a detector centrally on the safe door and...

Страница 13: ...Example h 62 w 55 d 29 1 Compute X1 h w 1 X1 62 55 X1 117 2 Compute X2 2d w 2 X2 2 x 29 55 X2 113 3 Find X minimum X1 X2 3 X 113 4 Compute J w d4 J 55 29 J 84 5 Find D maximum X J 5 D 113 Where h Safe Height w Safe Width d Safe Depth D Maximum Linear Distance This rule of thumb is valid for most available safe sizes However if any one dimension is very large or very small when compared to the othe...

Страница 14: ...power for mercantile alarms and 72 hours of standby power for bank vault alarms Typical UL Complete Vault Installations 1 Install in accordance with Underwriter Laboratories standard UL 681 2 Install EVD 1 detectors on interior walls ceilings and floors spaced as shown in Figure 7 Refer to Table 6 for maximum spacing on various materials 3 A detector must be installed on the vault door if the net ...

Страница 15: ... Coverage Steel plates at least 1 4 thick Minimum 8 0 11 3 x 11 3 8 x 13 9 10 x 12 5 15 x 5 6 Half 15 0 21 2 x 21 2 8 x 28 9 10 x 28 3 15 x 26 20 x 22 4 Maximum 20 0 28 3 x 28 3 8 x 39 2 10 x 38 7 15 x 37 1 20 x 34 6 Monolithic concrete at least 6 thick Minimum 16 0 22 6 x 22 6 8 x 31 0 10 x 30 4 15 x 28 3 20 x 25 0 Concrete block at least 6 thick Minimum 16 0 22 6 x 22 6 8 x 31 0 10 x 30 4 15 x 2...

Отзывы: