live. Cover screws must be torqued to a minimum of 2 N-m.
Engineer/Architect Specifi cations
Air pressure supervisory switch shall be a Model PS40-EXF as manufactured by Potter Electric Signal Co. of St. Louis, Mo. U.S.A. and shall be
installed on the sprinkler systems as shown on the drawings and/or as specifi ed herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the air supply line on the system side of any shut-off
valve. A Model BVL bleeder valve as supplied by Potter Electric Signal Co. of St. Louis, Mo. U.S.A., or equivalent, shall be connected between
the product and the air supply to provide a means of testing the operation of the supervisory switch.
The switch unit shall contain two SPDT (Form C) switches. One switch shall operate at a pressure decrease of 69 kPA/.69 BAR (10 PSI) from
normal. The second switch shall operate at a pressure increase of 69 kPA/.69 BAR (10 PSI) from normal. Switch contacts shall be rated at 15.0
Amps at 125/250 VAC and 2.0 Amps at 30 VDC. The units shall have a maximum pressure rating of 1724 kPA/17.24 BAR (250 PSI) and shall
be adjusted from 69kPA/.69 BAR (10 PSI) to 1207 kPA/12.07 BAR (175 PSI).