Wall-Mount Power Supply Chassis model 750003
3.3
Earthing Connector
C
AUTION
To ensure safety of personnel, Positron recommends following these guidelines:
Q
Each Chassis of an installation must be permanently connected to earth
using the ground lug on the front of the Chassis.
Q
The field wiring should include a readily-accessible disconnect device.
The disconnect device shall disconnect both poles (RTN and Live).
Q
This equipment must be located in the same immediate area (such as
adjacent cabinets) as the equipment it is powering.
Q
There shall be no switching or disconnecting devices in the earthed
circuit conductor between any Chassis of an installation and the point of
connection of the earthing electrode conductor.