background image

 
 

 

2.6.8.

 

Setting the pH regulation cycle time 

 

 

The cycle time is used to set the injection cycle of the pump, and, therefore, to take into account the reaction time of 
the pool between injection and measurement.  

 

The shorter the cycle, the more responsive the regulation will be. For very small pools, such as spas/Jacuzzis, use a 
30 second cycle.

 

 

Menu 

Possible settings 

Default setting 

pH regulation 
pH cycle 

From 30 to 300 sec, in 30-second increments 

60 sec 

 

2.6.9.

 

Setting the pH regulation thresholds 

 

Menu 

Sub-menu 

Possible settings 

Default setting 

pH regulation 
pH limits 

pH limits 

Upper Limit

 

Upper pH value above which the corresponding alarm 
will be activated 

8.0 

pH limits 

Lower Limit

 

Lower pH value below which the corresponding alarm 
will be activated 

6.0 

 

2.7.

 

Settings 

2.7.1.

 

Setting the date and time 

 

Menu

 

Possible settings

 

Default setting 

Settings 
Date       XX/XX/XX 

Day/Month/Year 

01/01/01 

Settings 
Time              XX:XX 

Hour/Minute 

random

 

 
 

2.7.2.

 

Selecting the display language 

 

Menu

 

Possible settings

 

Default setting

 

Settings 
Languages         EN 

 

French 

 

English 

 

Deutsch 

 

Español 

 

Italiano 

 

Nederlander 

 

Portugués 

French 

 
 

2.7.3.

 

Sensor settings 

 

CONNECTORS AT THE ‘Ext’ PLUG

 

Marking on the connector 

Sensor to be connected 

None 

pH TANK 

Empty pH container 

AUX. FLOW 

Auxiliary flow rate for pH corrector injection 

FLOW 

Measuring chamber flow 

 
 
 
 

Содержание PRO pH

Страница 1: ...PAPI004233 M Version 21 04 Notice d utilisation Instructions for use PRO pH R gulateur pH pH regulator FRANCAIS ENGLISH...

Страница 2: ...nsigne pH 8 2 6 6 Sp cification du type de correcteur pH 8 2 6 7 R glage de la plage proportionnelle de la r gulation pH 8 2 6 8 R glage du temps de cycle de la r gulation pH 9 2 6 9 R glage des seuil...

Страница 3: ...alimentation chambre de mesure 12 Raccord tuyau semi rigide 6 8mm 13 C ble bidon de correcteur pH vide 1 Panneau de r gulation 2 Coffret lectronique 3 Sonde pH 4 Capteur d bit 5 Pr filtre 6 Pompe de...

Страница 4: ...par pas de 0 1 Seuil Bas De 6 Consigne pH 0 2 par pas de 0 1 Date 01 01 01 Jour Mois Ann e Heure XX XX Heure Minute Version Logiciel XX XX Aucun affichage en lecture seule durant quelques secondes 2...

Страница 5: ...tiquement condition que ces fonctions ne soient pas d sactiv es et que certaines alarmes ne soient pas d clench es Mise l arr t du coffret lectronique faire un appui long condition qu aucune alarme ou...

Страница 6: ...tration Communication Modbus RS485 ID Code XXXXXXXX R gulation pH Ajustage Param tres Langues FR Historique Injection pH S N XXXX XXXXXX XXX R gulation pH Etalonnage Param tres Capteurs Adresse MAC XX...

Страница 7: ...ver OFF pour d sactiver ON 2 6 3 Ajustage de la mesure du pH Menu R glages possibles R glage par d faut R gulation pH Ajustage De 6 5 7 5 par pas de 0 1 7 2 6 4 Etalonnage de la sonde pH La sonde pH f...

Страница 8: ...Echou Effectuer une nouvelle fois la navigation avec les instructions ci dessus plusieurs fois si n cessaire Si l talonnage choue toujours remplacer la sonde puis effectuer de nouveau un talonnage 2 6...

Страница 9: ...pH Seuil Haut Valeur pH sup rieure au del de laquelle l alarme correspondante sera activ e 8 0 Seuils pH Seuil Bas Valeur pH inf rieure au del de laquelle l alarme correspondante sera activ e 6 0 2 7...

Страница 10: ...le tous les r glages effectu s configuration d usine 2 8 Historique de donn es Menu Sous menu Contenu Historique Etalonnage pH Date du dernier talonnage de la sonde pH Historique Filtration Filtration...

Страница 11: ...n du r seau reliant le coffret lectronique aux appareils connect s Ces param tres n apparaissent pas si le mode est r gl OFF Lors d une mise jour non automatique du logiciel du coffret lectronique eff...

Страница 12: ...i Bidon de correcteur pH vide Remplacer le bidon de correcteur pH Oui Alarme D bit Mesure Oui D bit d eau insuffisant dans la chambre de mesure V rifier que le capteur d bit est raccord au coffret lec...

Страница 13: ...rifier les r glages dans les menus R gulation pH Consigne R gulation pH Correcteur Acide R gulation pH Cycle pH Non Alarme Seuil Bas pH Oui Injection trop importante de correcteur acide V rifier les...

Страница 14: ...ts le fabricant se r serve le droit de modifier tout moment et sans pr avis les caract ristiques de ses fabrications La pr sente documentation n est fournie qu titre d information et n a aucune implic...

Страница 15: ...Setting the pH setpoint 8 2 6 6 Specification of the pH corrector type 8 2 6 7 Setting the proportional range of the pH regulation 8 2 6 8 Setting the pH regulation cycle time 9 2 6 9 Setting the pH...

Страница 16: ...connector 11 Valve for feeding the measuring chamber 12 Semi flexible tubing fitting 6 8 mm 13 Empty pH corrector container cable 1 Control panel 2 Electronics unit 3 pH probe 4 Flow sensor 5 Pre fil...

Страница 17: ...rom pH setpoint 0 2 to 8 in increments of 0 1 Lower Limit From 6 to pH setpoint 0 2 in increments of 0 1 Date 01 01 01 Day Month Year Time XX XX Hour Minute Software Version XX XX None read only displ...

Страница 18: ...regulation starts automatically provided that this function is not disabled and certain alarms have not been activated Switching off the electronics unit press and hold provided that no alarm or alert...

Страница 19: ...ltration Communication Modbus RS485 ID Code XXXXXXXX pH regulation Adjustment Settings Languages EN History pH injection S N XXXX XXXXXX XXX pH regulation Calibration Settings Sensors MAC address XXXX...

Страница 20: ...ion of the pH measurement Menu Possible settings Default setting pH regulation Adjustment From 6 5 to 7 5 in increments of 0 1 7 2 6 4 Calibrating the pH probe The original pH probe provided is alread...

Страница 21: ...amber or pH calibration Failed Perform the navigation again with the above instructions several times if necessary If calibration still fails replace the probe then perform another calibration 2 6 5 S...

Страница 22: ...n pH limits pH limits Upper Limit Upper pH value above which the corresponding alarm will be activated 8 0 pH limits Lower Limit Lower pH value below which the corresponding alarm will be activated 6...

Страница 23: ...warning Settings Reset Sett I Resetting the settings cancels all the settings carried out factory configuration 2 8 Data history Menu Sub menu Content History pH calibration Date of the last pH probe...

Страница 24: ...tion of the network connecting the electronics unit to the connected devices These settings do not appear if the mode is set to OFF During a non automatic update of the electronics unit software carri...

Страница 25: ...tion Alarm Empty pH container Yes pH corrector container empty Replace the pH corrector container Yes Alarm Flow Measurement Yes Insufficient water flow in the measuring chamber Check that the flow se...

Страница 26: ...heck the settings in the pH Regulation Setpoint pH Regulation Acid corrector pH regulation pH Cycle menus No Alarm Lower pH Limit Yes Too much acid corrector injected Check the settings in the pH Regu...

Страница 27: ...quality of its products the manufacturer reserves the right to modify the characteristics of the products at any time without notice This documentation is provided for information purposes only and i...

Страница 28: ......

Отзывы: