8
3.6.
Chlorine dosing
3.6.1.
Manual injection
Menu
Functions
Possible
settings
Setting
by default
Instructions
Dosing
Manual injection
•
Primes the pump and fills the
semi-rigid pipes
•
Injects chlorine
•
Means of checking that the
pump is working properly
From 1 to 59, in
1 min
increments
10 min
•
To start injecting:
Confirm the selected
setting.
(The pump is
running, and the timer
countdown is displayed in
real time).
•
To pause,
and to restart injection:
Press
OK
.
•
To stop injection:
Press
.
3.6.2.
Activating/disabling chlorine dosing
Menu
Possible settings
Default setting
Dosing
Mode XXX
•
ON
(to activate)
•
OFF
(to disable)
ON
3.6.3.
Calibrating the ORP probe
I
The pH sensor must be calibrated:
-
when first commissioning the equipment,
-
at the start of each season when the equipment is re-commissioned,
-
each time the probe is replaced.
1)
Open the 470 mV ORP calibration solution.
2)
Close the measuring chamber’s 2 supply valves
.
3)
If the probe is already installed:
Remove the probe from the probe holder, without disconnecting it.
If the probe is not already installed:
Connect the probe to the electronics unit.
4)
Go to the ‘
Dosing - ORP Calibration
’ menu.
5)
Navigate through the menus following the below instructions:
Dosing
ORP calibration
ORP calibration
Solution 470 mV
→
Insert the probe into the 470 mV ORP calibration solution, then wait a few minutes.
ORP calibration
In progress
→
Do not touch the probe.
(Wait a few seconds)
OK
OK