PU300/PU500 INSTALLATION MANUAL

 

  

 

 

                                            

 

10232-10.doc

Polyamp AB, Sweden 

www.polyamp.com 

Page 

4 (10) 

 

1  Before installation 

On the front panel label the following is displayed: 
Converter type name, input voltage range, nominal 
output voltage, serial number, options and article 
number. The converter type name consists of model 
name PU300 or PU500 followed by input code and 
output voltage. Two examples: 

 

”Type: PU300B24” has input code ”B” and 
nominal output voltage 24Vd.c. 

 

”Type: PU500 110/48” has input code ”110” 
and nominal output voltage 48Vd.c. 

Input, output and case are galvanically separated 
from each other. You can thus choose how you 
want the system connected.  

The input is protected against reverse polarity by a 
parallel diode at the input on models with input 
code A, B, 24 and 48. This diode, however, is only 
intended to blow an external input fuse. C, D, 110 
and 220 input codes have a series diode.  

The input shall be fused with an approved fuse with 
a slow blow characteristic and high breaking 
capacity

.

 See 

Table 1

PU300 input fuses

 

Input voltage code 

Time delay fuse 

A 35 

B 25 

C 8 

D 5 

 

PU500 input fuses

 

Input voltage code 

Time delay fuse 

24 30 

48 20 

110 

  8 A 

220 

  4 A 

Table 1. Recommended input fuses. 

 

There are two reasons why we do not include the 
fuse. 

1.

 

DC-networks should be fused at the distribution 
point to protect the cable.  

2.

 

Different applications require different types of 
fuses. 

If the converter is mounted in an electric vehicle, an 
external series diode on the input is recommended. 
Please contact your Polyamp dealer. 

If the converter supplies a DC-motor, we 
recommend an external parallel diode at the motor 
poles to protect against reverse voltages. 

For the disconnection ability, an external 
disconnection device, which is able to disconnect 
both polarities, shall be incorporated with the input 
power supply cord. The disconnection device must 
be properly labelled and easy accessible. 

2  Installation 

The converter shall be mounted in an enclosure, 
which meets the demands of EN60950 regarding 
fire, voltage hazard and mechanical strength. 

The converter is supplied with mounting plates. 
With these you can mount the converter in any 
direction. The converter is convection cooled and in 
order to get sufficient cooling there shall be a 
minimum of 30 to 50 mm space at upper and lower 
parts of the converter. If this is not possible, we 
recommend the use of an external fan. 

Note that the expected life of the converter is 
dependant on converter temperature. For every 
10

C that the temperature is lowered the expected 

life is approximately doubled. It is therefore crucial 
to cater for good ventilation and if possible to 
reduce ambient temperature. 

To meet the EMC specifications in the enclosed 
”declaration of conformity” use twisted-pairs for 
connecting input, output and alarm. Shielded cables 
are not necessary. 

1.

 

Connect protective earth to the connection 
marked no 40. Use a ring terminal that has been 
crimped by an appropriate tool

.  

2.

 

Connect the output. The converter output is 
short-circuit proof by a constant current limit 
which works unlimited in time. Therefore there 
is no need to fuse the load (unless you use 
multiple loads, see below). The current limit is 
fixed to 105% of nominal output current. 

 

If the converter is to be connected in parallel 
at the output, please consult 

3  Parallel

 

connection

 

on page 5. 

 

If you use multiple loads, please consult 

4  

Multiple loads at the

 output on page 6. 

 

If you intend to use the alarm, please consult

 

6

  Alarm on page 7.  

 

If you intend to use output voltage sense, 
please consult 

5

  Sense on page 7. 

 

If you intend to use inhibit, please consult 

7

  

Inhibit on page 8. 

 

3. 

 

Connect the input cables. Bundle input cables 
together at the terminals separated from the 
output cables. Make the same

 arrangement on 

the output side. This is to make sure one 

Содержание PU300

Страница 1: ...PU300 PU500 INSTALLATION MANUAL 10232 10 doc Polyamp AB Sweden www polyamp com Page 1 10 PU300 PU500 Installation manual ...

Страница 2: ...e of printing However the information may have been updated since then Polyamp AB reserves the right to make changes in this manual without notice The exclamation point within an equilateral triangle is intended to alert the user to presence of important operating and maintenance instructions in the literature accompanying The lightning flash with arrowhead within an equilateral triangle is intend...

Страница 3: ...L SENSE 7 6 ALARM 7 7 INHIBIT 8 8 OUTPUT OVER VOLTAGE PROTECTION 8 9 ISOLATION VOLTAGE TEST 8 9 1 DC ISOLATION TEST OUTPUT TO CASE 8 9 2 DC ISOLATION TEST INPUT TO OUTPUT AND INPUT TO CASE 8 9 3 AC ISOLATION TEST INPUT TO OUTPUT AND INPUT TO CASE 9 9 4 AC ISOLATION TEST SIGNAL TERMINALS TO CASE 9 9 5 DC ISOLATION TEST SIGNAL TERMINALS TO CASE 9 9 6 AC ISOLATION TEST ALARM TO INHIBIT TERMINALS 9 10...

Страница 4: ...with the input power supply cord The disconnection device must be properly labelled and easy accessible 2 Installation The converter shall be mounted in an enclosure which meets the demands of EN60950 regarding fire voltage hazard and mechanical strength The converter is supplied with mounting plates With these you can mount the converter in any direction The converter is convection cooled and in ...

Страница 5: ...ith another power supply or if you require redundant operation If a converter breaks down with an internal short circuit on the output and other converters are connected in parallel on the output the broken unit will short circuit the others if the series diode is not used This might cause excessive heat or even fire in the faulty unit If the series diode is used the alarm relay will switch to ALA...

Страница 6: ...fore the series diode as in Figure 4 ii Repeat from i until you reach the desired output voltage at the load 5 To achieve good current sharing adjust all converters so that the voltage difference before the series diode is 0 00V between all units that are connected in parallel and so that the voltage at the load is still the desired 4 Multiple loads at the output If you are using several loads we ...

Страница 7: ...e load and not at the output of the converter and does thereby compensate for voltage drop in the cables between the converter and the load The maximum voltage compensation is 5 of nominal output voltage Do not disconnect the negative power connection from the converter to the load before the positive when the converter is running and external sense is used This might damage the converter and it i...

Страница 8: ... c 2 5kVa c 4kVd c Alarm Inhibit 2 5kVa c 4kVd c Table 2 Isolation test voltages If your AC isolation test equipment cannot supply enough current you can perform a DC isolation test with 4000Vd c 2500V x 2 x 1 1 4000Vd c where 1 1 safety factor 9 1 DC isolation test output to case 1 Disconnect all cables from the converter 2 Connect the input terminals of the converter to case 3 Connect the output...

Страница 9: ...ster from 0V to corresponding value in Table 2 Check that the leakage current does not exceed 5µA The voltage should not be applied for more than a few seconds or the Y capacitors might be damaged 5 Turn off the isolation tester and discharge the test voltage with a 10 M resistor between the signal terminals and case 9 6 AC isolation test alarm to inhibit terminals 1 Disconnect all cables from the...

Страница 10: ...d Connect the input again and measure the output voltage If the converter now starts the load was too heavy or there was a short circuit If there is an external short circuit remove it If the load is too large decrease the load or consult your Polyamp dealer 5 The unit is broken Contact your Polyamp dealer 11 2 The input fuse blows when the input is connected 1 Check that the input voltage polarit...