ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
15
Figure 15.
Figure 16.
Figure 17.
7.2
Grouping Zones
For ease of control operation, multiple zones can be grouped together. The
grouped zones are treated as one group with its own name and turned on or off
together. Individual balanced damper position is not affected by grouping,
which means zone balancing can be conducted before or after grouping.
Grouping can be carried out as follows:
a) In ‘Installer Settings’ screen (Figure 6), touch to enter ‘Grouping’
screen (Figure 15).
7.3
Balancing Zones
Remote balancing feature of ZONETOUCH V2 offers the flexibility of balancing
the amount of airflow to each zone electronically. Once the opening position of
the damper is set, the damper will only open to this position. The default setting
for each damper is 100% opening position and the adjustable range is between
10% and 100%. The balancing settings can be conducted on the touch screen
as below.
a) In ‘Installer Settings’ screen (Figure
6), touch
b) The system will show a prompt
(Figure 17) and then enter the
‘Balancing’ screen (Figure 18).
b) Touch the edit field of the group, and buttons will appear.
c) Touch or button to add or minus zones to the group
d) Repeat steps b) and c) to define all groups.
NOTE: The maximum number of zones in a group is four. The zones to be
grouped will be consecutive zones. The factory default for grouping is that
each group has one zone.