ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
14
Similarly if bypass set-point is reached, the screen displays ‘Bypass is Activated’
as shown in Figure 13.
Spill/Bypass Settings
a) In the ‘Parameter’ screen (Figure 7), touch the option buttons of spill or bypass
to select spill mode or bypass mode.
b) Touch spill/bypass edit field to make it editable, and then and
buttons will appear.
c) Touch or button to change the spill/bypass set-point to required
value. The adjustable range is from 0% to 50% with 10% increments.
IMPORTANT: DO NOT set spill/bypass set-point to 0% unless there is a
permanent open zone used as spill zone. Otherwise, there will be no spill
zone when all zones are closed and damage may be caused by high
pressure build up inside ducts if air conditioner is running.
Figure 12.
Figure 13.
Figure 14.
7.1.5 Installer Settings Password
The password which will be used in
Figure 5 is to prevent unauthorized
changing of the installer settings.
To reset this password, touch the
password edit field in the ‘Parameter’
screen (Figure 7), and then type in the
new password and touch ‘Enter’ key
to confirm the password change
(Figure 14).