4. Supply Air Safety High & Low Limits

 

   

 

For safety reasons, the system monitors the    

 

 

   

 

supply air temperature closely. 

 

   

 

If the temperature moves outside of the limits,    

 

 

   

 

all dampers in the system are forced open and     

 

   

 

the LCD displays 

‘Safety’

 on screen. 

 

   

 

The factory default supply air safety high & low   

 

   

 

limits are 60

o

C and 5°C respectively and safety   

 

   

 

control is disabled.  

 

   

 

1)  At the setting mode, press            button until the    

 

   

 

 

LCD displays the 

‘H_limit’

 screen. 

 

   

 

2)  Press            or            button to change the high    

 

   

 

 

limit to the desired value. The adjustable range  

 

 

   

 

 

of the high limit is from 45°C to 75°C.

 

   

 

3)  Press  button once again, the LCD screen will  

 

 

   

 

 

display the 

‘L_Limit’

 

   

 

4)  Press            or            button to change the low    

 

   

 

 

limit to the desired value. The adjustable range  

 

 

   

 

 

of the low limit is from 0°C to 15°C.

If the customer does not want the safety function, the supply air 
sensor is not needed to be installed. The safety H_limit and L-limit 

MUST be disabled by pressing           button during the setup. 

5. Spill/Bypass Air Setpoint

Spill/Bypass air is primarily used to relieve duct pressure for the safety 
of the ducting. Such a control is achieved by comparing the system 
requirement with a setpoint. The factory default is in spill mode and the 
setpoint is 30% of the total number of zones, which is equivalent to 30% of 

the total airflow across the fan coil. 

Содержание Zonemaster Unipoint

Страница 1: ...UNIPOINT CONTROL SYSTEM Setup Guide Polyaire Pty Ltd 11 13 White Road GEPPS CROSS South Australia 5094 Tel 08 8349 8466 Fax 08 8349 8446 www polyaire com au...

Страница 2: ......

Страница 3: ...n the System 10 4 Supply Air Safety High Low Limits 11 5 Spill Bypass Air Setpoint 11 6 Naming Zones 13 7 Damper on off Test 13 Information Sheet 14 Trouble Shooting Guide 15 Specifications 16 Liabili...

Страница 4: ...lised zone labelling Auto spill bypass the designated zones bypass are forced open when all zones are turned off Safety system Opens all dampers if the supply air temperature is less than low limit or...

Страница 5: ...per drives the blade of the damper to turn on off the air from ducting to a zone 4 Bridge Cable Bridge cable connects the damper controller and the motorised damper together 5 Supply Air Sensor Supply...

Страница 6: ...ct the touchpad dampers and power supply in series via a control bus as shown on Figure 1 Figure 2 shows another connection in which a double adaptor is used to connect the touchpad in the middle of t...

Страница 7: ...Page 4 Figure 2 Wiring diagram 2...

Страница 8: ...e damper controller 2 Allocate and set unique addresses to all zones with consideration of spill privileges for the zones Please refer to the Zone Address section for details Please note that bypass d...

Страница 9: ...not plug the damper controller into any other motorised damper except a Polyaire authorised one 4 Apply the power to the transformer by plugging in the transformer into the 240VAC power outlet 5 Plug...

Страница 10: ...be on If not check the cable and the connection 7 Repeat the step 6 until all damper controllers are connected together in series and all LED lights are on 8 Use another pre tested cable to connect t...

Страница 11: ...damper controllers again All of the LED lights must be flashing in one second interval Otherwise check the cable and the connection 12 Turn off the power and disconnect the touchpad 13 Position the to...

Страница 12: ...in Figure 3 When allocating address to each zone in spill mode it is strongly recommended to give lower addresses to those zones that have higher spill privileges The lower the address the higher the...

Страница 13: ...ameter and provides more accurate temperature display 1 Using an accurate probe to measure the temperature of the area you want to calibrate and record the value 2 At the setting mode press button unt...

Страница 14: ...from 45 C to 75 C 3 Press button once again the LCD screen will display the L_Limit 4 Press or button to change the low limit to the desired value The adjustable range of the low limit is from 0 C to...

Страница 15: ...mber of open zones is less than its setpoint The bypass damper is also serially connected with other dampers and has a special address as mentioned before 1 At the setting mode press button until the...

Страница 16: ...reset zone names for the zone 3 To make changes to the preset selected name press button to move to the character that is flashing 4 Use or button to select the character from the list as desired Ther...

Страница 17: ...to assist installation and commissioning Address Default Name Custom Name Zone_1 Zone_2 Zone_3 Zone_4 Zone_5 Zone_6 Zone_7 Zone_8 Parameter Default Value Custom Value O F Zone Z1 Z8 High limit disable...

Страница 18: ...he battery at first Reset the touchpad by turning off and turning on the power supply again If the display is normal plug in the battery again Dampers have no response when turning it on or off Check...

Страница 19: ...tive humidity 10 to 80 Avoid static electricity hazards Avoid electromagnetic radiation sources Avoid dust contamination Avoid highly corrosive environments Touchpad Power input 24VAC 50Hz Dimensions...

Страница 20: ......

Отзывы: