Page 10
RECOMMENDED COMMISSIONING PROCEDURE
1. Initiating and Exit Setting Process
The Zonemaster UniPoint has several parametres that must be set in the
commissioning stage.
1) Hold down both and buttons
for about 5 seconds until the LCD displays
‘Setting’
on the top line of the LCD screen.
2) At the setting mode, pressing button at any
time will return to the normal operation mode.
2. Room Temperature Sensor
The touchpad has an onboard sensor to measure the temperature of
the room for indication purpose. The sensor can be calibrated by the
parameter and provides more accurate temperature display.
1) Using an accurate probe to measure the
temperature of the area you want to calibrate
and record the value.
2) At the setting mode, press button
until the LCD displays the
‘Sensor’
screen.
3) Press or button to adjust the
displayed value to the record value.
3. Number of Zones in the System
For the purpose of zone status display and spill/bypass zone
calculation, the controller needs to know the total number of
on/off zones in the system. Its factory default value is 8.
1) At the setting mode, press button until the
LCD displays the
‘O/F Zone’
screen.
2) Press or button to adjust the number
of zones to the total number of the zones installed.
It can be selected from 1(show
‘Zone 1’
) to 8
(show
‘Z1—Z8’
).