background image

Fire detecti on line module MLD-61/62

The  MLD-61/62  enables  to  connect  of  two  fire  detection  lines/

loops.  The  MLD-61  is  equipped  with  27  V  line  voltage  converter 

which  enables  to  power  up  to  4  detection  lines/loops.  In  order 

to minimalize the current consumption and to expand the number 

detection lines/loops, it is recommended to use one MLD-61 toge-

ther with one MLD-62. Each detection line can support up to 250 

adresseble line elements.

Input/output module MKS-60

The module is equipped with:

-  two potential-free relay outputs with max load 1 A/30 V,

-  two potential outputs (signaling lines) with 0,5 A/24V,

-  two low voltage monitoring inputs.

The module is fail-safe ready and the position of the relay or its ope-

ration in case of fault can be programmed. Inputs and outputs are 

equipped with external line continuity monitoring circuits. Monito-

ring  input  can  be  programmed  as  2-states  (quiescent  and  action) 

or 3-states (quiescent, action 1 and action 2). States are identified 

by different resistance of the line.

Signaling lines module MWS-60

Monitoring inputs module MWK-60

High voltage relay outputs module MPW-61

Relay outputs module MPK-60

The module is equipped with 4 signaling lines with 0,5 A/30 V. Out-

puts are equipped with external line continuity monitoring circuits. 

The  module  is  equipped  with  8  resistance  monitoring  inputs.  In-

puts  are  equipped  with  external  line  continuity  monitoring  circu-

its.  They  can  be  programmed  as  2-states  (quiescent  and  action) 

or 3-states (quiescent, action 1 and action 2). States are identified 

by different resistance of the line.

The module is equipped with:

-  two high voltage potential-free relay outputs with 5 A/230 V AC,

-  two monitoring inputs.

Inputs and outputs are equipped with external line continuity mo-

nitoring circuits. Monitoring input can be programmed as 2-states 

(quiescent and action) or 3-states (quiescent, action 1 and action 2). 

States are identified by different resistance of the line.

The  module  is  equipped  with  4  relay  potential-free  outputs  with  

current load up to 1 A/30 V. The module is fail-safe ready and the 

position of the relay or its operation in case of fault can be program-

med. Outputs are equipped with external line continuity monito-

ring circuits.

Printer MD-60

The module is equipped with the controller and the thermal printer 

mechanism.

Conventi onal lines module MLK-60

The module is equipped with 8 conventional lines to connect co-

nventionl detectors and manual call points. 

Conventi onal detecti on line module MLK-61

The MLK-61 allows to connect up to eight conventi onal detecti on li-

nes/zones. Each conventi onal detecti on line can operate with up to 

32 detectors or 10 manual call points.

All these lines are supervised for conti nuity and short-circuit.

Содержание POLON 6000

Страница 1: ...FIRE DETECTION AND ALARM SYSTEM POLON 6000 ...

Страница 2: ...ules and no des well fitted to individual building requirements Such solution enables the arrangement of the control panel equipment installed in required locations This provides maximum optimization of the system reduction costs of installation All that is possible thanks to implementation of doubled main processor controllers communi cation buses and connections between nodes The POLON 6000 cont...

Страница 3: ...ring circuits The module is equipped with 8 resistance monitoring inputs In puts are equipped with external line continuity monitoring circu its They can be programmed as 2 states quiescent and action or 3 states quiescent action 1 and action 2 States are identified by different resistance of the line The module is equipped with two high voltage potential free relay outputs with 5 A 230 V AC two m...

Страница 4: ...rame for max four functional modules assembly brackets WP 61 WL 62 and WP 63 WP 64 dedicated for installation of assembly frame either at the top or at the bottom part of the cabinet cables with different length for communication and power supply distribution within the node Transmission modules MTI secure the data bus of the control panel MTI 61 is a transmission module without separation The modu...

Страница 5: ... its non volatile memory and are reada ble from the control panel after its installation in the detector line Fire detectors The 6000 model range detectors are analogue detectors with pro grammable sensitivity using the control panel This ability enables an adjustment of detectors response time to the phenomena occur ring in detector vicinity All detectors are equipped with automatic sensitivity s...

Страница 6: ...etc and also supervision of their efficient operation Seven types of elements allow their optimal use in the installation EKS 6044 4 in 4 out EKS 6022 2 in 2 out EKS 6004 4 out EKS 6040 4 in EKS 6202 2 in 2 out high voltage EKS 6400 4 in high voltage EKS 6222P 2 high power HV outputs 2 HV inputs 2 LV inputs I O modules technical data EKS 6040 210 μA EKS 6022 220 μA EKS 6004 EKS 6044 240 μA EKS 620...

Страница 7: ...battery or de tection line and external power supplier The selected sources of po wer are monitored The strength of the sound is independent from the selected source of the power Technical data Operating voltage from 16 5 to 24 6 V External power supplier voltage from 9 6 V to 30 V Current consumption from detection line 150 µA Max current consumption from power supplier 50 mA Max sound pressure 1...

Страница 8: ...ossible control outputs 64000 Number of control outputs on one loop 256 Number of non potential potential control outputs on the functional modules 1000 600 Number of all supervision inputs 64000 Number of supervision inputs in one detection loop 256 Number of supervision inputs in functional modules 1200 FUNCTIONAL DIAGRAM OF THE POLON 6000 CONTROL PANEL ul Glinki 155 85 861 Bydgoszcz POLAND phon...

Отзывы: