background image

Overview

The POLON 6000 control panel 

with a distributed architecture

The addressable, interacti ve POLON 6000 fi re alarm system is a set 

of  latest  technology  equipment,  designed  for  very  fast  detecti on 

and signaling of fi re, precise indicati on of fi re origin, control of fi re 

protecti on safety devices, and informati on of appropriate interven- 

ti on services or building guards about fi re. It enables protecti on of 

mid-size, large and very large faciliti es, especially so called “intelli- 

gent” buildings with huge amount of fi re protecti on safety devices. 

POLON 6000 can be easily integrated with variety of existi ng buil-

ding management systems. Due to its specifi c features it enables 

to arrange perfect set of necessary devices, well-fi tt ed to site re-

quirements.

The POLON 6000 system is based on newly designed control panels 

with distributed architecture and new range of line elements. All 

devices of the POLON 6000 system meet requirements of the latest 

editi on of EN 54 European Standards.

The POLON 6000 control panel design was based on the idea of a 

module device with a distributed architecture. It consists of many 

unified modules of various types, installed inside standardized ca-

binets.  Cabinets  can  be  arranged  as  separate  units  or  combined 

in sets (so called nodes) and can be located in different places of 

site  area,  even  if  those  locations  are  distant.  All  modules  within 

one  node  and  nodes  between  themselves  are  connected  with 

a common, doubled (redundant) digital communication bus. 

Each control panel can be flexibly assembled with modules and no- 

des  well-fitted  to  individual  building  requirements.  Such  solution 

enables the arrangement of the control panel equipment, installed 

in required locations. This provides maximum optimization of the 

system, reduction costs of installation. All that is possible thanks to 

implementation of doubled main processor controllers, communi-

cation buses and connections between nodes.

The  POLON  6000  control  panel  consists  of  the  PSO-60  operation 

panels with 10’’ touch screen, functional modules: detection lines 

MLD-61 and MLD-62, input-output MKS-60, relay outputs MPK-60, 

signalling  outputs  MWS-60,  conventionale  line  module  MLK-60, 

high  current  relay  outputs  MPW-61,  supervision  inputs  MWK-60, 

supply MZP-60 and transmission MTI-61, MTI-62, MTI-63 v2.

PSO panels and modules are installed inside the cabinets with stan- 

dard dimensions, which can be mechanically binded. A set of such 

mechanically connected cabinets create a control panel node. The 

control panel need to have at least one node in which main con-

trol panel PSO-60 (having number 1) is installed. This is the “main 

node” of the control panel. There is always only one “Main node” 

in the system. The rest of elements (modules) of the control panel 

is  configured  in  form  of  external  nodes  which  are  connected  to 

the “main node”. The communication between nodes is provided 

by double cable connection (RS-485) or double fiber optic cables. 

Each node shall be equipped – depending on the size of node and 

expected current consumption – with one or more supply modules. 

Each node can contain line modules with connected detection lines, 

input-output modules for direct control or supervision of fire safety 

devices. In each external node the PSO-60 panel can be implemen-

ted, acting as the parallel operation panel.

Содержание POLON 6000

Страница 1: ...FIRE DETECTION AND ALARM SYSTEM POLON 6000 ...

Страница 2: ...ules and no des well fitted to individual building requirements Such solution enables the arrangement of the control panel equipment installed in required locations This provides maximum optimization of the system reduction costs of installation All that is possible thanks to implementation of doubled main processor controllers communi cation buses and connections between nodes The POLON 6000 cont...

Страница 3: ...ring circuits The module is equipped with 8 resistance monitoring inputs In puts are equipped with external line continuity monitoring circu its They can be programmed as 2 states quiescent and action or 3 states quiescent action 1 and action 2 States are identified by different resistance of the line The module is equipped with two high voltage potential free relay outputs with 5 A 230 V AC two m...

Страница 4: ...rame for max four functional modules assembly brackets WP 61 WL 62 and WP 63 WP 64 dedicated for installation of assembly frame either at the top or at the bottom part of the cabinet cables with different length for communication and power supply distribution within the node Transmission modules MTI secure the data bus of the control panel MTI 61 is a transmission module without separation The modu...

Страница 5: ... its non volatile memory and are reada ble from the control panel after its installation in the detector line Fire detectors The 6000 model range detectors are analogue detectors with pro grammable sensitivity using the control panel This ability enables an adjustment of detectors response time to the phenomena occur ring in detector vicinity All detectors are equipped with automatic sensitivity s...

Страница 6: ...etc and also supervision of their efficient operation Seven types of elements allow their optimal use in the installation EKS 6044 4 in 4 out EKS 6022 2 in 2 out EKS 6004 4 out EKS 6040 4 in EKS 6202 2 in 2 out high voltage EKS 6400 4 in high voltage EKS 6222P 2 high power HV outputs 2 HV inputs 2 LV inputs I O modules technical data EKS 6040 210 μA EKS 6022 220 μA EKS 6004 EKS 6044 240 μA EKS 620...

Страница 7: ...battery or de tection line and external power supplier The selected sources of po wer are monitored The strength of the sound is independent from the selected source of the power Technical data Operating voltage from 16 5 to 24 6 V External power supplier voltage from 9 6 V to 30 V Current consumption from detection line 150 µA Max current consumption from power supplier 50 mA Max sound pressure 1...

Страница 8: ...ossible control outputs 64000 Number of control outputs on one loop 256 Number of non potential potential control outputs on the functional modules 1000 600 Number of all supervision inputs 64000 Number of supervision inputs in one detection loop 256 Number of supervision inputs in functional modules 1200 FUNCTIONAL DIAGRAM OF THE POLON 6000 CONTROL PANEL ul Glinki 155 85 861 Bydgoszcz POLAND phon...