SANDOR PLUS SMA
POLITEC | INSTALLATION MANUAL - VER.2.6
17.2 Receiver optics
J4 tester signal
Power supply
SW4 heaters
Additional tamper
24V
12V
1 2
3 4 5 6 7
ON
RX1
1 2 3
4
5 6
ON
RX2
ON
RX3
ON
RX4
With DIP 7 in ON (as default) and when the power supply LED lights up, the functioning of the RX optic
is verified.
The power supply of the heaters is set by default to 24V; 12V can be used by changing the jumper
configuration (SW4) on all optics and on the MES 9 C board.
The voltage can be both AC and DC.
Jumper J4 reads the value of the alignment signal, expressed in volts.
N.B.:The settings relating to the addressing of the optics are already set by default.
N.B.:The barrier can result in an alarm even if the WEAK SIGNAL LED is off.The cause may be the lack
of synchronism or a misaligned transmitter.
Weak signal LED
Test button
Test LED