Politec S.r.l. | Manual SADRIN – Ver. 3.3
8
4.
CONNECTIONS
Use screened cables for connection, linking screen to negative of supply -12VDC (GND) on terminal block. In
addition to ordinary supply cables, tamper and alarm relay, you MUST connect transmitter side to receiver
SADRIN TX - SADRIN RX with a two-wire for the synchronization (+sync TX to + SincRX) (-sync TX to, -
sync RX).
Only for expansions MUST be set in ON a DIPSWITCH (3-10) on relative bench. Beam 1 and 2
always selected, because built-in motherboard.
Tamper
+ Sinc.
- Sinc.
Supply
12Vdc
Tamper NC
Alarm NC
100- 500 mA
RX
Supply
12Vdc
Tamper NC
+ Sinc.
- Sinc.
TX
Tamper
+
-
+
-