0000300349/230420/0 MDB-Diluter PRO
20
The HMI starts the installation wizard.
• Complete the installation wizard.
Refer to paragraph 5.3 and 5.3.1 for more
information about the VFD (frequency inverter) and
the PID setpoint.
Select the question mark on the touch
screen for extensive explanation on all
settings.
?
5.2
Extraction fan
• Turn the main switch (refer to Fig. 6.1F) to “
off
” and open
the Panel.
• Turn the bar that is connected to the main switch to
energize the Panel manually.
• Push the START/STOP FAN button (refer to
start the fan.
• Make sure that the direction of rotation of the motor is
correct.
If the direction of rotation of the motor is not correct:
• Invert any two connections (96/97/98) on the VFD to
change the motor direction.
• Push the button again to stop the fan.
5.3
VFD (frequency inverter)
The VFD is integrated in the Panel. The fan speed is controlled
by the system pressure. To operate the system, you must
know or determine the airflow in the duct that is necessary to
get the correct throw and air circulation.
The required system pressure must be programmed in the HMI
to keep the airflow at a constant level, independently from the
(increasing) pressure drop caused by the filter cartridges. This
system pressure is called the ‘PID setpoint’, which arranges
the necessary fan speed (Hz) accordingly.
The table below indicates the throw related to the airflow and
fan speed
25
.
Throw
Airflow/
nozzle
Total airflow
Frequency
20 m (65 ft)
1000 m�/h
(590 CFM)
6000 m�/h
(3530 CFM)
30 Hz
40 m (130 ft)
1500 m�/h
(885 CFM)
9000 m�/h
(5300 CFM)
50 Hz
For more detailed information, refer to Fig. X on page 31.
Fig. XI shows the horizontal throw per nozzle.
5.3.1 PID setpoint of the fan pressure
To determine and set the PID setpoint, do the following.
• Go to the Settings menu on the HMI.
• Enter PIN.
• Select menu
PID setpoint of the fan pressure
(or enter
2.2.1
on the numeric keypad).
25. All nozzles 100% open
• Select the button
Start fan
.
•
Measure the actual airflow with a flowmeter. Best
measuring position: approx. 500 mm (20 in.) below the
outlet unit of the MDB-Diluter.
• Use the buttons
+
or
─
to determine the setpoint to reach
the desired airflow. At this setpoint, the frequency must
not exceed 45Hz.
• Select
Stop fan
when the desired airflow is reached.
• Select
Finish
to exit the screen. The new values will be
saved.
Fig. 5.1 PID setpoint
6
USE
WARNING
During use, always use Personal Protective
Equipment (PPE) to avoid injury. This also applies
for persons who enter the work area.
6.1
Control equipment
6.1.1 Panel
The control panel contains the following controls and
indicators:
Outside
Fig. 6.1 (also refer to Fig. V on page 28)
A White LED | POWER ON
- LED
off: system is off
- LED blinking: system is starting up
- LED on: system is ready
B Green LED | FAN RUNNING
-
LED off: fan is off
- LED blinking: fan is ramping down
26
- LED on: fan is running
C Yellow LED | WARNING
-
LED off: no problem
- LED on
27
: refer to the HMI for the cause of the warning
D Red LED | ALARM
-
LED off: no problem
- LED on
28
: refer to the HMI for the cause of the alarm
E Buzzer | acoustic signal
- together with the ALARM signal (D)
- in some cases: together with the WARNING signal (C)
F Main switch
26. Ramp down time: 60 seconds
27. The system continues to run
28. The system stops running