0000112607/010420/A ControlGo 

13

In case of 

one

 (1) SCS system: proceed with 

chapter 6.

In the Learning Mode you “teach” the Panel about the size of 

the filter system;

 

-

MDB: the number of filter cartridges (min. 2, max. 64)

 

-

SCS: the number of filter systems (1 or 2; default setting: 1)

At the same time, the Learning Mode verifies the cable 

connections of the SlaveBoard(s) and the correct setting of the 

DIP switches. 

WARNING

You must go through the Learning Mode procedure 

to make sure that all SlaveBoards of the filter 

modules are correctly connected. If you fail to do 

so, it can finally lead to a malfunction of the filter 

cleaning system.

5.3.1  General

• 

Follow the flowchart GENERAL on page 20.

In case of an MDB system: 

•  Proceed with paragraph 5.3.2

In case of two SCS systems:

•  Proceed with paragraph 5.3.3

5.3.2  MDB

• 

Follow the flowchart MDB on page 21.

5.3.3 

SCS (two filter systems)

• 

Follow the flowchart SCS (#2) on page 22.

USE

6.1 

Control panel

The control panel contains the following controls and 

indicators:

Fig. 6.1 (also refer to Fig. V on page 18)

A  White LED | POWER ON

 

- LED

 off: system is off

 

- LED blinking: system is starting up

 

- LED on: system is ready

B  Green LED | FAN RUNNING

 

-

LED off: fan is off

 

- LED blinking: fan is ramping down

30

 

- LED on: fan is running

C  Yellow LED | WARNING

 

-

LED off: no problem

 

- LED on

31

: the blinking pattern shows the cause of the 

warning; refer to paragraph 6.3.1

D  Red LED | ALARM

 

-

LED off: no problem

 

- LED on

32

: the blinking pattern shows the cause of the 

alarm; refer to paragraph 6.3.2

E  Main switch
F  Green button | START/STOP FAN

 

- to start and stop the fan manually

 

- to reset the precoat timer (push and hold for 20 seconds)

30.  Ramp down time: 60 seconds
31.  The system continues to run
32.  The system stops running

G  Black button | FILTER CLEANING

 

-

to activate an additional filter cleaning cycle

 

- to suppress the buzzer (push and hold for 5 seconds)

33

 

- to reset the warning and alarm LED (push and hold for 5 

seconds) 

H  Buzzer | acoustic signal

 

- together with the ALARM signal (D)

 

- in some cases: together with the WARNING signal (C)

I  Tumbler switch 0-1 | Normal Mode / Service Mode

 

- normal use: Panel in Normal Mode (1)

 

- during service/maintenance/repair activities: put the 

Panel in Service Mode (0)

34

 

Fig. 6.1 

0 = Service Mode

1 = Normal Mode

A

B

C

D

E

F

I

G

H

Control panel 

6.2 

Use

6.2.1  Start/stop fan

You can start and stop the fan in two ways:

 

- manually by the START/STOP FAN button (ref. Fig. 6.1F)

 

- automatically

35

 by an external signal from e.g. a welding 

robot or a timer

6.2.2  Filter cleaning

The filter cleaning system can be activated in two ways:

 

- automatically, pressure controlled (refer to paragraph 2.2.1)

 

- manually by the FILTER CLEANING button (ref. Fig. 6.1G)

36

 

37

6.2.3  Service Mode

When you put the Panel in the Service Mode (ref. Fig. 6.1I), 

the fan stops running immediately. In case the filter cleaning 

system is active, it stops as well. 

In the Service Mode, you can only start

38

/stop the fan and the 

filter cleaning system manually. The automatic functions are 

disabled. 

33.  You must still solve the cause of the alert
34.

  In Service Mode you can only activate the fan and the filter system manually

35.  Stop delay: 3 minutes for removal of after fumes, if any
36.

  You cannot stop/interrupt the filter cleaning cycle

37.

  You cannot activate this button during the first 40 running hours of the system 

and within 40 running hours after filter replacement, to maintain the protective 

layer of precoat material on the filter cartridges

38.

  The filter cleaning system continues to run. Push the black button again or put 

the Panel in Normal Mode to stop it. 

Содержание CONTROLGO

Страница 1: ...www plymovent com Control panel CONTROLGO Installation and user manual EN...

Страница 2: ...ument and is therefore subject at any time to change or amendment and the right to change or amend is hereby expressly reserved The instructions in this publication only serve as a guideline for insta...

Страница 3: ...ControlGo of Plymovent is an intelligent control panel including the required connection cables This system controls the compressed air valves of the connected filter system MDB or SCS and the connec...

Страница 4: ...rtificates CE 1 6 Ambient conditions 1 6 1 ControlGo Panel Pressure sensors Ambient temperature internal external min nom max 0 C 32 F 20 C 68 F 50 C 122 F 20 C 4 F 20 C 68 F 50 C 122 F Max relative h...

Страница 5: ...n EN ISO 12100 1 is the use for which the technical product is suited as specified by the manufacturer inclusive of his directions in the sales brochure In case of doubt it is the use which can be ded...

Страница 6: ...es approuv es et sch mas lectrique des armoires en question ATTENTION Risque de tension lectrique Il pourrait tre n cessaire d installer un interrupteur principal pour mettre hors tension la machine a...

Страница 7: ...n wire A and the cable jacket B Heat shrink the shrink tube with a heat gun C C A B C B 15 Recommended cable specifications use cables with a max wire diameter 1 5 mm AWG 16 All cables 3 Put the wires...

Страница 8: ...0 IN 10 11 24V 12 IN 11 13 24V 14 IN 12 15 COM2 16 GND Digital input 6 12 1 24V 2 IN 6 3 24V 4 IN 7 5 24V 6 IN 8 7 24V 8 IN 9 9 24V 10 IN 10 11 24V 12 IN 11 13 24V 14 IN 12 15 COM2 16 GND Valves 1 24V...

Страница 9: ...SlaveBoard SlaveBoard including conduit conduit connectors M20 nuts 2x Tube clamp screw Due to the cable length you can only make horizontal and vertical connections It is not possible to make diagon...

Страница 10: ...he correct sequence start with the upper left filter module 1 address from left to right subsequently from top to bottom 24 The red module on the PC board Addressing sequence Address configuration pos...

Страница 11: ...rm signal from an external device27 start stop signal cable 4 alarm signal cable 5 remove the wire bridge from input IN 11 27 E g a welding robot or a timer Indicator LED s Valves Digital input 1 5 CA...

Страница 12: ...ressure sensor Remove the wire bridge from input IN 4 refer to Fig 4 6A Indicator LED s Valves Digital input 1 5 CAN Slave Digital input 6 12 Filter Pressure sensor Light tower Power Relay 1 Relay 2 2...

Страница 13: ...Push the START STOP FAN button ref Fig 6 1F to start the fan Push the button again to stop the fan Filter cleaning system 3 MDB only Push the FILTER CLEANING button ref Fig 6 1G to activate the filter...

Страница 14: ...tem continues to run 32 The system stops running G Black button FILTER CLEANING to activate an additional filter cleaning cycle to suppress the buzzer push and hold for 5 seconds 33 to reset the warni...

Страница 15: ...MODUS MODE DE SERVICE MODO SERVICIO EXTERNAL DEVICE EXTERN APPARAAT EXTERNES GER T DISPOSITIF EXTERNE DISPOSITIVO EXTERNO External device In the ALARM mode the fan system stops immediately 7 MAINTENA...

Страница 16: ...ective Repair or replace the fan motor connection Repair or replace the fan control equipment NO COMPRESSED AIR GEEN PERSLUCHT KEINE DRUCKLUFT ABSENCE D AIR COMPRIM FALTA DE AIRE COMPRIMIDO COMMUNICAT...

Страница 17: ...l rules EN IEC 61131 2 2007 Programmable controllers Part 2 Equipment requirements and tests EN IEC 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial...

Страница 18: ...rolGo 17 ANNEX Fig I Dimensions Panel A C D E F B mm in A 435 17 1 B 400 15 7 C 400 15 7 D 425 16 7 E 225 8 9 F 210 8 3 Fig II SlaveBoards Fig III SlaveBoard PC board CAN OUT CAN IN Fig IV Connection...

Страница 19: ...ILTERSVERSTOPT FILTER GES TTIGT FILTRES OBSTRU S FILTROS OBSTRUIDOS NO COMPRESSED AIR GEEN PERSLUCHT KEINE DRUCKLUFT ABSENCE D AIR COMPRIM FALTA DE AIRE COMPRIMIDO COMMUNICATION ERROR COMMUNICATIEFOUT...

Страница 20: ...ssed air switch 9 Filter pressure sensor PT 2500 H05VV F 3G0 5 10 SCS Slave valve H05VV F 3G0 75 11 Fan control direct online H05VV F 4X0 5 12 Control cable SCS valve compressed air switch H05VV F 5G0...

Страница 21: ...l open B Push and hold the black button Turn the main switch on at the same time Continue to hold the button the white LED shows a heartbeat blinking pattern Learning Mode is starting up C When the gr...

Страница 22: ...5 seconds B Make sure that the number of flashes corresponds with the number of filter cartridges C If NOT and the buzzer sounds no filter cartridges are detected at all Push the black button during 5...

Страница 23: ...FAN SCS 2 SCS 2 ready A B Flowchart SCS 2 Explanatory notes A By default the yellow LED blinks one time with an interval of 5 seconds B Push the green button to change the setting from 1 to 2 filter s...

Страница 24: ...mware update has failed Possible causes failure during the update process corrupt update files on the USB stick you have tried to upload an older firmware version than the existing one you have tried...

Страница 25: ...www plymovent com 0000112607 010420 A ControlGo...

Отзывы: