15
reduced automatically, without loss of
heating
comfort
by
reducing
fuel
consumption.
Decrease of preset temperature in selected
time intervals is indicated by the symbol “S”
on the main screen.
To activate time intervals, set the parameter
Night time decrease for the given heating
circuit to ON. The parameter Decrease set
the temperature reduction, one for all time
intervals.
Night time decreases can be defined
separately for every day of the week set
Schedule.
Select temperature reduction and beginning
and end of respective time interval. The time
intervals for 24 hours are fixed at 30min.
Time periods.
Night time decrease for boiler
In the setting time intervals the boiler works.
Outside of these time intervals, the boiler is
turned off.
8.20
Circulating pump control
The settings for the circulating pump can be
found in the menu:
Night time decrease
and
Service settings
→
CH and HUW settings
Setting of circulating pump control is
analogical to night decrease setting.
Circulating pump switches on in selected
time intervals. In disregarded time intervals
circulating pump will start and remain in
operation for the period of time set in
Circulating pump operation time , then will
stop and remain out of operation for the
period of time set in Circulating pump
standstill time.
8.21
Fuel level setup
Activating the fuel level gauge
In order to enable display of the fuel level,
set value of parameter
Menu
→
Boiler settings
→
Fuel level
→
Alarm level
to a value greater than zero, e.g. 10%.
Tip: fuel level can also be seen in room panel
ecoSTER200 and ecoSTER TOUCH.
Operation of fuel level indicator
Any time upon filling fuel tank, press and
hold
pressed current fuel level value.
Following prompt appears:
Set fuel level at 100% Once selected and
confirmed YES, fuel level is set at 100%.
Once selected and confirmed YES, fuel level
is set to 100%.
Note: Fuel may be replenished at any time
without a need to wait for complete empty
fuel tank. Replenish fuel always to the level
corresponding to 100% level of the fuel tank
and set 100% level as described above.
Description of operation
The regulator calculates the fuel level basing
on the current fuel consumption. Default
settings do not always correspond to the
actual consumption of fuel by the given
boiler, therefore, for proper operation this
method requires the regulator user to
perform level calibration. No additional fuel
level sensors are required.
Calibration
To perform calibration - fill the fuel tank to
the level corresponding to its full load and
set the parameter:
Boiler settings
→
Fuel Level
→
Fuel level
calibration
→
Fuel Level 100%
The indicator in the main window will be set
to 100%. On-going calibration process is
signalled by flashing fuel level gauge. The
gauge will flash until the time of marking the