20 

 

11.11

 

Connecting  temperature  limiter 

STB 

In  order  to  prevent  the  boiler  from 
overheating 

due 

to 

the 

regulator 

malfunction,  a  safety  temperature  limiter, 
appropriate  for  the  given  boiler  and  heating 
system, should be fitted.  
The limiter can be connected to terminals 1-
2,  as  specified  in  Drawing  12  .  When  the 
limiter activate, the fan power supply will be 
disconnected.  

 

The  temperature  limiter  must 
have nominal operating voltage of 
at least ~230V, and it should have 
the applicable permits. 

 
If the limiter is not connected to terminals 1-
2,  a  bridge  should  be  made.  The  bridge 
should be made of wire the section of which 
is  at  least  0,75  mm

2

,  with  insulation  thick 

enough  to  comply  with  the  boiler  safety 
requirements.  

 

The  current  regulations  demand 
that  a  safety  temperature  limiter 
is used. 

11.12

 

Connecting 

additional 

thermal 

protection  

The  ecoMAX  200  regulator  can  be  equipped 
with additional thermal protection, type DZT-
1. This is an optional equipment, available to 
special  order.  It  cuts  off  the  fan  power 
supply.  Sensor  of  the  additional  thermal 
protection,  which  operates  on  low  safe 
voltage, 

should 

be 

placed 

in 

the 

thermometric  pipe  of  the  water  jacket.  You 
should  provide  good  thermal  contact  of  the 
DZT-1  sensor,  and  secure  it  against  coming 
loose from the measured surface.  
If the boiler temperature exceeds the DZT-1 
sensor activation temperature (85°C or 90°C 
±5  depending  on  the  DZT-1  type),  the  fan 
power supply is cut off. The fan power supply 
will be automatically restored after the boiler 
temperature drops by 10-20 degrees Celsius. 
If  a  DZT-1  sensor  is  not  connected,  an 
electric  bridge  should  be  made  at  terminals 
11-12.  

 

The 

additional 

thermal 

protection  cannot  be  used 
instead  of  the  mandatory 
safety temperature limiter! 

11.13

 

Smooth fan start 

During  every  activation  of  the  fan,  the 
regulator  gradually  increases  the  airflow 
power, which decreases the risk of explosion 
of  gases  accumulated  in  the  boiler.  This 
advantage  is  of  particular  significance  in  the 
case of fine coal boilers. 
 
The  fan  starts  smoothly  from 

Minimum 

revolutions 

  to  power  resulting  from  the 

algorithm within the P5 time (manufacturer‟s 
parameter – fan starting time). 
 

Содержание ecoMAX 200 W

Страница 1: ...oiler regulator ecoMAX 200 W FOR SOLID FUEL BOILERS WITH A FAN OPERATION AND MAINTENANCE MANUAL ISSUE 1 3 APPLICABLE TO SOFTWARE 10 034 10 035 10 036 2010 04 14 Dzia Zintegrowanego Systemu Zarz dzania...

Страница 2: ......

Страница 3: ...1 CONNECTING TEMPERATURE LIMITER STB 20 11 12 CONNECTING ADDITIONAL THERMAL PROTECTION 20 11 13 SMOOTH FAN START 20 12 Service settings 21 12 1 CENTRAL HEATING PUMP ACTIVATION TEMPERATURE N0 21 12 2 B...

Страница 4: ...erature limiter Therefore it cannot be used instead of a safety temperature limiter The value of the programmable parameters should be selected appropriately to the parameters of the given boiler and...

Страница 5: ...rtable temperature in the heated rooms 3 Information about documentation The regulator manual is a supplement for the boiler manual In particular except for this manual the boiler manual should also b...

Страница 6: ......

Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX 200 W...

Страница 8: ...ng the preset boiler temperature due to hot utility water heating 10 signal decreasing the preset boiler temperature due to operation of the room thermostat 11 service menu symbol 12 hot utility water...

Страница 9: ...l the arrow is in the boiler regulation mode position Use or buttons to set value The method is based on the T1 boiler indication and consists in decreasing of the airflow power from Maximum revolutio...

Страница 10: ...the PID EMISSION mode Moreover after equipping the regulator with an emission sensor it is possible to enable very fast detection of fuel shortage This provides additional saving of heat energy resul...

Страница 11: ...temperature exceeds the preset boiler temperature by 10 C In the SUPERVISION mode the fan is enabled cyclically for short periods in order to prevent the fire from going out and to remove accumulated...

Страница 12: ...e regulator outputs The window shown at Drawing 5 appears and the central heating pump symbol flashes first Drawing 5 Manual control Press START and STOP to change the status of the given output START...

Страница 13: ...REGULATOR INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX 200 W...

Страница 14: ...d by the regulator where 1 ecoMAX 200 regulator 2 central heating pump 3 hot utility water pump 4 fan 5 room thermostat 6 hot utility water tank 7 central heating system 8 chimney duct 9 boiler T1 boi...

Страница 15: ...of 15 60 C During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 11 Regulator installation 11 1 Environmental conditions Due to the risk of ex...

Страница 16: ...ermal conditions and safety issues a safe distance between active parts of the terminals and the conductive metal elements of the enclosure must be kept Drawing 10 Metal elements of the regulator encl...

Страница 17: ...d with an arrow Drawing 12 Diagram of electric connections with external devices where T1 boiler temperature sensors type CT4 T2 hot utility water temperature sensors type CT4 T3 emission temperature...

Страница 18: ...at least 0 5mm2 Total length of the sensor leads cannot exceed 15 m The boiler temperature sensor CT4 should be fitted in the thermometric pipe situated in the boiler shell Hot utility water temperatu...

Страница 19: ...be filled via hot utility water pump select the hot utility water pump operation mode acc to point 7 9 11 10 Connecting room thermostat To make the boiler more economical and the temperature in the h...

Страница 20: ...l order It cuts off the fan power supply Sensor of the additional thermal protection which operates on low safe voltage should be placed in the thermometric pipe of the water jacket You should provide...

Страница 21: ...eating pump is activated This protects the boiler against retting caused by its being cooled down by hot water returning from the system Disabling the central heating pump on its own does not guarante...

Страница 22: ...e in the heated rooms will drop and the boiler will reach the preset temperature faster and switch to the SUPERVISION mode Yet too long a blockade of the central heating pump will cause the system to...

Страница 23: ...the hot utility water pump when the central heating pump is disabled In order to cool the boiler down operation of the hot utility water pump can be extended by the time r4 Extending hot utility wate...

Страница 24: ...he cases of power supply failure the regulator will resume the operation mode in which it was before the failure 13 Firmware WARNING Values of the following parameters can be modified only by qualifie...

Страница 25: ...threshold Thanks to this a momentary exceeding of the boiler temperature will not cause stoppage of the boiler Before the boiler reaches the P0 temperature the regulator will attempt to drop the exces...

Страница 26: ...temperature limiter STB input jumper is on terminals 1 2 the jumper should be placed only if no temperature limiter is connected check if the additional thermal protection sensor input jumper is on te...

Страница 27: ......

Отзывы: