Combustion Air

COMBUSTION AIR

1 . Locate combustion air assembly at an exterior location which is 
not likely to be accidentally blocked in any manner . Locate assem-
bly a min . of 12” above the snow line to prevent blockage by snow 
accumulation .
2 . Never mount the combustion air inlet assembly in a garage or 
storage area where combustible fumes such as gasoline might be 
drawn into the fireplace .
3 . Combustion air can be drawn from the crawl space under a house 
when an adequate supply of air is provided by open ventilation .
4 . CAUTION: Do not take combustion air from attic space or garage 
space .
5 . Locate air supply inlet at least 3’ away from any appliance vent 
terminal .
6 . Avoid extremely long runs and numerous turns in the duct leading 
from the fireplace to the combustion air assembly . These conditions 
increase the resistance to the free flow of air through the duct . 

The use of outside air for combustion is optional unless required by 
building codes . It is only necessary to supply outside combustion air 
to one side of the fireplace . Use the open air kit .

OUTSIDE AIR KIT ASSEMBLY (OAK100)

1 . Place the insulation gasket between the open air kit starting collar 
and fireplace wall .
2 . Place the starting collar (4”) on the side of fireplace . Fasten it in 
place with the four sheet metal screws provided .

NOTE: When the air starting collar is securely attached, it will form 
a seal against the fireplace wall.

WARNING!

Do not use a combustible duct . Always use UL Listed Class 0 or 1 
duct material .

3 . Attach outside duct to starting collar with duct clamp or screws . 
4 .  Cut  a  6-inch  diameter  opening  for  the open air kit  in  the 
outside wall covering where the outside vent is to be located . 
5 . Select and cut a piece of duct long enough to attach to the 
fireplace and stick out at  least 3” beyond the face of the wall to 
which the open air kit inlet air vent will be attached . Cut duct with 
a standard pocket knife .

6 . If the duct is the insulated type, push the insulation back from one 
end of the duct approximately 2” . 
7 . Slip the exposed end of the duct over the starting collar on the 
fireplace .
8 . Using the sheet metal screws provided, secure the duct end to the 
collar attached to the fireplace .
9 . Nail or screw the combustion air assembly to the surface of the 
wall .

 

A

Insulation Gasket

PHOAK Starting Collar

(4) Sheet Metal Screws

ZC Firebox

RH Side

Fig.     - Outside Air Inlet Collar Attachment

PHOAK Inlet Air Vent

PHOAK Starting Collar

4" Semi-Rigid Metal

 Vent Tube

Fig.    - Simple Outside Air Kit Installation

Notice: If you do not install an outside air kit be sure to 
keep the lever in the “closed” position to avoid cold air 
drafts .

Figure 13 - Outside Air Inlet Collar Attachment

Figure 14 - Simple Outside Air Kit Installation

Figure 12 - Outside Air Operation

 

A

OUTSIDE AIR LEVER

OPEN

CLOSED

Содержание PHZC32C

Страница 1: ...he fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Carefully review the instructions supplied with the decorative type unvented r...

Страница 2: ...ation 10 Gas Line Installation 11 Combustion Air 12 Optional Outside Air Kit 12 Optional Equipment 13 Replacement Parts PHZC32C PHZC36C PHZC42C 14 PHZC32F PHZC36F PHZC42F 15 Warranty 16 WARNING This p...

Страница 3: ...void any drafts that alter burner flame patterns Do not allow fans to blow directly into fireplace Do not place a blower inside burn area of firebox Ceiling fans may create drafts that alter burnerfla...

Страница 4: ...These spaces must be maintained to prevent the firebox from coming in contact with combustible materials WARNING Do not attempt to burn solid wood fuels vented gas log sets or any other combustible i...

Страница 5: ...ES Phillips screwdriver Square Framing materials Hammer Saw and or saber saw Tee joint Level Pipe wrench Measuring tape Pliers Electric drill and bits Fireplace surround materials noncombustible Caulk...

Страница 6: ...traffic or windy or drafty areas DO NOT INSTALL WHERE CURTAINS FURNITURE CLOTHING OR OTHER FLAMMABLE OBJECTS ARE LESS THAN 42 FROM FRONT OF HEATER Never obstruct the front opening of the vent free fi...

Страница 7: ...34 3 4 36 1 2 21 1 2 36 34 3 4 40 1 2 21 1 2 42 34 3 4 46 1 2 21 1 2 Figure Framing Dimensions A B C C Figure Corner Framing Dimensions MINIMUM CORNER FRAMING DIMENSIONS Firebox Size A B C 32 31 1 2 6...

Страница 8: ...N clearance to a combustible back wall 4 Mantel clearances The canopy hood supplied with the unit must be installed If a combustible mantel is installed it must meet the clearance require ments as sho...

Страница 9: ...are safe to overlay the black painted metal face including radiant plates and do not pose a fire hazard Any noncombustible finish material must not extend past or interfere with the fireplace opening...

Страница 10: ...hood and Firebox as shown in Figure 11a 4 Then tighten all screws securely WARNING Close fireplace screen panel before operating a decorative type unvented room heater WARNING The firebox canopy must...

Страница 11: ...ntrols and burners Failure to do so could prevent the heater from operat ing reliably Consult applicable codes An external regulator must be used on all propane L P G heaters in addition to the regula...

Страница 12: ...crews provided NOTE When the air starting collar is securely attached it will form a seal against the fireplace wall WARNING Do not use a combustible duct Always use UL Listed Class 0 or 1 duct materi...

Страница 13: ...Lower Grill Assembly 4 8 Sheet Metal Screws 4 Sheet Metal Screws Included in Blower Kit Figure 15 Optional Blower Installation Blower Installation Instructions 1 Lower the bottom grill assembly and r...

Страница 14: ...tom Grill Assembly 1 ZCF A7002 ZCF A5012 ZCF A5012 FIREBOX COMPONENTS CURTAIN SCREEN CURTAIN SCREEN ROD BOTTOM GRILL ASSEMBLY CIRCULATING FIREBOX TOP GRILL ASSEMBLY RH PANEL LH PANEL CENTER PANEL Fig...

Страница 15: ...ig Radiant Firebox Assembly CANOPY HOOD PHZC32F PHZC36F PHZC42F Ref Description Qty PHZC32F PHZC36F PHZC42F 4 Outside Air Kit 1 OAK100 OAK100 OAK100 5 Brick Panel Sets 1 ZRP320 ZRP360 ZRP420 5 1 Cente...

Страница 16: ...result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a de...

Отзывы: