Gas Line Installation

WARNING!

Plumbing connections should only be performed by a qualified, 
licensed plumber . Main gas supply must be off when plumbing 
gas line to fireplace or performing service .

Consult all local codes . All gas piping must be installed to comply 
with local codes, or in the absence of local codes, with the latest 
edition of the National Fuel Gas Code ANSI Z223 .1/NFPA54 .
The 1/2” gas line may enter either from the left side or right side 
of  the firebox . Gas access holes are provided on  both sides of the 
firebox .
A listed manual shutoff valve must be installed upstream of the 
appliance . A union tee and plugged 1/8” NPT pressure tapping point 
should be installed upstream of the appliance .

IMPORTANT: Install main gas valve (equipment shutoff valve) in 
an accessible location. The main gas valve is for turning on or 
shutting off the gas to the fireplace.

A sediment trap may be upstream of the heater to prevent moisture 
and contaminants from passing through trap to the  heater  controls  
and  burners . Failure to do so could  prevent the heater from operat-
ing reliably . Consult applicable codes .
An external regulator must be used on all propane/L .P .G . heaters, 
in  addition to  the   regulator fitted    to  the   heater, to reduce the 
supply tank pressure to 13” w .c . (maximum) . 
Any copper tubing used to supply propane / L .P .G . from 
the tank must be internally tinned . 

NOTE:
When connecting propane / L.P.G. vent-free room heaters, you 
must use pipe sealant resistant to propane / L.P.G.
IMPORTANT: Hold heater regulator with a wrench to prevent move-
ment when connecting to inlet piping.
Check gas type: The gas supply must be the same as stated  on  
the  heater’s  rating  plate.  If the gas supply is different, DO NOT 
INSTALL THE HEATER. Contact your dealer for the correct model

WARNING!

Connecting directly to an unregulated propane / L .P .G . tank can 
cause an explosion .

WARNING!

Do no connect directly to natural gas 1/2 PSI or 2 PSI systems . 
Always make sure natural gas pressure is regulated 10 .5 w .c . 
(maximum before operating the unit) .

After completing connection, test all gas joints from the gas meter to 
the gas heater regulator for leaks . Using soap and water solution or a 
gas sniffer . DO NOT USE AN OPEN FLAME .

Содержание PHZC32C

Страница 1: ...he fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Carefully review the instructions supplied with the decorative type unvented r...

Страница 2: ...ation 10 Gas Line Installation 11 Combustion Air 12 Optional Outside Air Kit 12 Optional Equipment 13 Replacement Parts PHZC32C PHZC36C PHZC42C 14 PHZC32F PHZC36F PHZC42F 15 Warranty 16 WARNING This p...

Страница 3: ...void any drafts that alter burner flame patterns Do not allow fans to blow directly into fireplace Do not place a blower inside burn area of firebox Ceiling fans may create drafts that alter burnerfla...

Страница 4: ...These spaces must be maintained to prevent the firebox from coming in contact with combustible materials WARNING Do not attempt to burn solid wood fuels vented gas log sets or any other combustible i...

Страница 5: ...ES Phillips screwdriver Square Framing materials Hammer Saw and or saber saw Tee joint Level Pipe wrench Measuring tape Pliers Electric drill and bits Fireplace surround materials noncombustible Caulk...

Страница 6: ...traffic or windy or drafty areas DO NOT INSTALL WHERE CURTAINS FURNITURE CLOTHING OR OTHER FLAMMABLE OBJECTS ARE LESS THAN 42 FROM FRONT OF HEATER Never obstruct the front opening of the vent free fi...

Страница 7: ...34 3 4 36 1 2 21 1 2 36 34 3 4 40 1 2 21 1 2 42 34 3 4 46 1 2 21 1 2 Figure Framing Dimensions A B C C Figure Corner Framing Dimensions MINIMUM CORNER FRAMING DIMENSIONS Firebox Size A B C 32 31 1 2 6...

Страница 8: ...N clearance to a combustible back wall 4 Mantel clearances The canopy hood supplied with the unit must be installed If a combustible mantel is installed it must meet the clearance require ments as sho...

Страница 9: ...are safe to overlay the black painted metal face including radiant plates and do not pose a fire hazard Any noncombustible finish material must not extend past or interfere with the fireplace opening...

Страница 10: ...hood and Firebox as shown in Figure 11a 4 Then tighten all screws securely WARNING Close fireplace screen panel before operating a decorative type unvented room heater WARNING The firebox canopy must...

Страница 11: ...ntrols and burners Failure to do so could prevent the heater from operat ing reliably Consult applicable codes An external regulator must be used on all propane L P G heaters in addition to the regula...

Страница 12: ...crews provided NOTE When the air starting collar is securely attached it will form a seal against the fireplace wall WARNING Do not use a combustible duct Always use UL Listed Class 0 or 1 duct materi...

Страница 13: ...Lower Grill Assembly 4 8 Sheet Metal Screws 4 Sheet Metal Screws Included in Blower Kit Figure 15 Optional Blower Installation Blower Installation Instructions 1 Lower the bottom grill assembly and r...

Страница 14: ...tom Grill Assembly 1 ZCF A7002 ZCF A5012 ZCF A5012 FIREBOX COMPONENTS CURTAIN SCREEN CURTAIN SCREEN ROD BOTTOM GRILL ASSEMBLY CIRCULATING FIREBOX TOP GRILL ASSEMBLY RH PANEL LH PANEL CENTER PANEL Fig...

Страница 15: ...ig Radiant Firebox Assembly CANOPY HOOD PHZC32F PHZC36F PHZC42F Ref Description Qty PHZC32F PHZC36F PHZC42F 4 Outside Air Kit 1 OAK100 OAK100 OAK100 5 Brick Panel Sets 1 ZRP320 ZRP360 ZRP420 5 1 Cente...

Страница 16: ...result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a de...

Отзывы: