Installation and user guide for PLATINUM® inverters 3800 TL, 3801 TL, 4300 TL, 4800 TL, 5300 TL, 6300 TL, 7200 TL
Errors and troubleshooting
No.
Meaning
Measure
Blocking errors
1000
...
1030
Blocking system error
▪
Isolate inverter from network and from DC
generator
▪
Put inverter back into operation
If measures prove unsuccessful:
▪
Inform service
1040
DC voltage too high
▪
Check module connection
1050
reverse polarity at DC
voltage connection
▪
Set DC disconnect to 0
▪
Check DC voltage connection
1060
...
1290
Blocking system error
▪
Isolate inverter from network and from DC
generator
▪
Put inverter back into operation
If measures prove unsuccessful:
▪
Inform service
1300
L and N connections mixed
up
▪
Check L and N at the AC voltage connection
1310
...
1990
System error
▪
Isolate inverter from network and from DC
generator
▪
Put inverter back into operation
If measures prove unsuccessful:
▪
Inform service
Non-blocking errors
2010
Amplitude limit for feed-
in phase exceeded or
undershot
▪
Arrange for voltage amplitude of feed-in
phase to be checked
2020
...
2040
Grid amplitude error phase-
to-phase voltage
▪
Ensure that all safety devices are switched
on
▪
Ensure that all three phases are connected
2080
Network fault on feed-in
phase (voltage peak)
If this occurs frequently:
▪
Arrange for all contacts and safety devices
to be checked, from the service connection
to the inverter
▪
Arrange for the network quality to be
checked