 1 INFORMATION ON THIS DOCUMENT

1.1 Function

The present operating instructions provide information on installation, connection and 
safe use for the following articles: 

CS AT-0•••••

CS AT-1•••••

.

1.2 Target audience

The operations described in these operating instructions must be carried out by quali-
fied personnel only, who are fully capable of understanding them, and with the techni-
cal qualifications required for operating the machines and plants in which the safety 
devices are to be installed.

1.3 Application field

These instructions apply exclusively to the products listed in paragraph Function, and 
their accessories.

1.4 Original instructions

The Italian language version is the original set of instructions for the device. Versions 
provided in other languages are translations of the original instructions.

 2 SYMBOLS USED

 This symbol indicates any relevant additional information

 Attention: Any failure to observe this warning note can cause damage or mal-

function, including possible loss of the safety function.

 3 DESCRIPTION

3.1 Device description

The safety device described in this manual is defined according to the Machinery 
Directive 2006/42/EC as logic component for safety functions.
The safety modules to which these usage instructions refer are devices specifically 
designed and manufactured for use on industrial machines. Upon opening of at least 
one channel, the safety function ensures that the safety relays open their output con-
tacts within the defined reaction time. The safety outputs of the module are enabled 
only if the channels CH1 and CH2 are consistently closed and after activating the 
START signal. If there is no supply voltage, the module deactivates the safety outputs 
within the specified release time.

3.2 Device functions

 This device is suitable for the following applications: as a module for emergency 

stop, for end position monitoring with movable guards, in safety circuits up to category 
3 (delayed contacts) and category 4 (instantaneous contacts) acc. to EN ISO 13849-1, 
up to SIL 3 acc. to EN 62061 and up to PL e acc. to EN ISO 13849-1. 
- The SIL 3 / PL e safety function is only available with the two redundant inputs 
configuration.
- Input with 1 or 2 channels.
- Output contacts: 2 instantaneous NO safety contacts, 1 instantaneous NC auxiliary 

contact,  2  delayed  NO  safety  contacts  (articles  CS  AT-0•••••).  3  instantaneous  NO 
safety contacts, 2 delayed NO safety contacts (CS AT-1•••••).

- Choice between automatic start, manual start or monitored start.

 With reference to the "automatic" operating mode, consider RES 1.2.3 of the 

Machinery Directive 2006/42/EC: "For machinery functioning in automatic mode, the 
starting of the machinery, restarting after a stoppage, or a change in operating condi-
tions may be possible without intervention, provided this does not lead to a hazardous 
situation".
- "Delay off" function: upon deactivation of the outputs with instantaneous contacts, 
the relays of the delayed contacts are also deactivated after a fixed or adjustable 
delay time.
- Connection of input channels of opposite potentials;
- Can be connected to semiconductor outputs and to magnetic safety sensors;
- Short circuit detection function of the control elements by means of safety system 
with self-monitoring and redundancy;
- Indicator LEDs for the switching state of the relays with instantaneous contacts 
(CH1, CH2), of the relays with delayed contacts (CH3, CH4) as well as of the supply 
voltage (PWR).
- In the event of a failure, the device switches to a safe state and deactivates the 
safety output.
- Without muting input, no bridging of the safety function.
- Screw terminals or plug-in terminals with screw connections or spring terminals (de-
pending on the model).
- Snap-mounting on DIN rails.

3.3 Intended use of the device

- The device described in these operating instructions is designed to be applied on 
industrial machines.
- The direct sale of this device to the public is prohibited. Installation and use must be 
carried out by qualified personnel only.
- The use of the device for purposes other than those specified in these operating 
instructions is prohibited.
- Any use other than as expressly specified in these operating instructions shall be 
considered unintended by the manufacturer. 
- Also considered unintended use:
a) using the device after having made structural, technical, or electrical modifications 
to it;
b) using the product in a field of application other than as described in paragraph 
TECHNICAL DATA.

 4 OPERATION

4.1 Operating diagram

Automatic 
start:

A1/A2

S11/S12

S21/S22

31/32

47/48, 57/58

13/14, 23/24, 33/34

t

C

t

A

t

R1

t

A

t

R2

t

R1

t

R2

t

A

t

R

t

C

Monitored 
start:

A1/A2

S11/S12

S21/S22

S33/S34 (START)

13/14, 23/24, 33/34

31/32

47/48, 57/58

t

MIN

t

A

t

R1

t

A

t

R2

t

R1

t

R2

t

A

t

R

Manual start:

A1/A2

S11/S12

S21/S22

S33/S34 (START)

31/32

47/48, 57/58

t

MIN

t

A

t

R1

t

R2

t

A

t

R

t

R1

t

R2

13/14, 23/24, 33/34

Legend:

t

MIN

:

 Min. duration of start impulse

t

C

:

 Simultaneity time

t

A

:

 Response time

t

R1

:

 Release time

t

R

:

 Release time in absence of power 

supply

t

R2

:

 adjustable release time for delayed 

contacts (see section TECHNICAL 
DATA)

Notes: The configurations with one channel are obtained taking into consideration the 
S11/S12 input only. In this case it is necessary to consider times t

R1

and t

R2

 referred to 

input S11/S12, time t

R

 referred to the supply, time t

A

 referred to input S11/S12 and to 

the start, and time t

MIN

 referred to the start.

4.2 Wiring diagrams

Emergency stop circuits

Input configuration with manual start

1 channel

Input configuration with manual start

2 channels

S33

S21

S22

S35

S34

A2

S31

S11

S12

A1

L / +

N / -

CS AT-0

•••••

CS AT-1

•••••

S33

S21

S22

S35

S34

A2

S31

S11

S12

A1

N / -

L / +

CS AT-0

•••••

CS AT-1

•••••

Semiconductor outputs

Input configuration with manual start

1 channel

Input configuration with manual start

2 channels

24 Vdc

+

-

OSSD

S31

S33

S21

S22

S35

S34

S12

A1

A2

CS AT-0

•••••

CS AT-1

•••••

24 Vdc

+

-

S31

S33

S21

S22

S35

S34

S12

CS AT-0

•••••

CS AT-1

•••••

A1

A2

OSSD1 OSSD2

S34

S34

Automatic start

With regard to the indicated diagrams, short-circuit the S33 
and S34 terminals in order to activate the automatic start 
module.

S21

S22

S21

S22

S35

S35

Monitored start

With regard to the indicated diagrams, remove the connec-
tion between the S22 and S35 terminals in order to activate 
the monitored start module.

Содержание CS AT-0 Series

Страница 1: ...nabile si disattivano anche i relè dei contatti ritardati Collegamento dei canali d ingresso a potenziali opposti Collegabile a circuiti d uscita a stato solido e sensori magnetici di sicurezza Funzione di rilevamento del cortocircuito degli organi di comando tramite sistema di sicurezza con autocontrollo e metodo di ridondanza Indicatori LED dello stato di commutazione dei relè con contatti istan...

Страница 2: ...la macchina dove il dispositivo è installato viene utilizzata per un uso diverso da quello specificato il dispositivo potrebbe non fornire una protezione efficace per l operatore La categoria di sicurezza del sistema secondo EN ISO 13849 1 comprendente il dispositivo di sicurezza dipende anche dai componenti esterni ad esso collegati e dalla loro tipologia Prima dell installazione assicurarsi che ...

Страница 3: ...elettrica 100 000 cicli di manovre Grado di inquinamento esterno 3 interno 2 Tensione ad impulso Uimp 4 kV Tensione nominale di isolamento Ui 250 V Categoria di sovratensione II Distanze in aria e superficiali secondo EN 60947 1 9 3 Alimentazione Tensione di alimentazione nominale Un 24 Vac dc 50 60 Hz art CS AT 024 120 Vac 50 60 Hz art CS AT 120 230 Vac 50 60 Hz art CS AT 230 Tolleranza sulla ten...

Страница 4: ...layed contacts are also deactivated after a fixed or adjustable delay time Connection of input channels of opposite potentials Can be connected to semiconductor outputs and to magnetic safety sensors Short circuit detection function of the control elements by means of safety system with self monitoring and redundancy Indicator LEDs for the switching state of the relays with instantaneous contacts ...

Страница 5: ...luding the safety device also depends on the external components connected to it and their type Before installation make sure the device is not damaged in any part Before commissioning check the correct functioning of the module according to the instructions of the operating diagrams see paragraph OPERATION Avoid excessive bending of connection cables in order to prevent any short circuits or powe...

Страница 6: ...T 230 Supply voltage tolerance 15 of Un Max DC residual ripple in DC 10 Power consumption AC 10 VA Power consumption DC 5 W 9 4 Control circuit Protection against short circuits PTC resistance Ih 0 5 A PTC times Response time 100 ms release time 3 s Maximum resistance per input 50 Ω Current per input 40 mA Min duration of start impulse tMIN 100 ms Response time tA 150 ms Release time tR1 25 ms Rel...

Страница 7: ...ion que cela n entraîne pas de situation dangereuse Fonction Delay Off lors de la désactivation des sorties instantanées les relais des contacts retardés sont également désactivés après une délai fixe ou sélection nable Raccordement des canaux d entrée à potentiels opposés Associable à des circuits de sortie à l état solide et des capteurs magnétiques de sécurité Fonction de détection du court cir...

Страница 8: ...i la machine munie de ce dispositif est utilisée à des fins autres que celles qui sont spécifiées le dispositif pourrait ne pas protéger l opérateur de manière efficace La catégorie de sécurité du système selon EN ISO 13849 1 comprenant le dispositif de sécurité dépend aussi des composants extérieurs qui y sont reliés et de leur typologie Avant l installation s assurer que le dispositif est totale...

Страница 9: ...e pollution externe 3 interne 2 Tension à impulsion Uimp 4 kV Tension nominale d isolement Ui 250 V Catégorie de surtension II Distances dans l air et superficielles selon EN 60947 1 9 3 Alimentation Tension d alimentation nominale Un 24 Vac dc 50 60 Hz art CS AT 024 120 Vac 50 60 Hz art CS AT 120 230 Vac 50 60 Hz art CS AT 230 Tolérance sur la tension d alimentation 15 d Un Ondulation résiduelle ...

Страница 10: ...vierung der Ausgänge mit Sofortkontakten werden auch die Relais der verzögerten Kontakte nach einer festen oder einstellbaren Verzögerungszeit deaktiviert Anschluss von Eingangskanälen mit entgegengesetzten Potenzialen An Halbleiterausgänge und magnetische Sicherheits Sensoren anschließbar Funktion zur Kurzschluss Erkennung der Befehlsgeber durch Sicherheits System mit Eigenüberwachung und Redunda...

Страница 11: ...er umgangen noch entfernt oder auf sonstige Art unwirksam gemacht werden Sollte die Maschine an der das Gerät montiert ist für einen anderen als den bestim mungsgemäßen Gebrauch verwendet werden so besteht die Möglichkeit dass das Gerät keinen ausreichenden Personenschutz gewährt Die Sicherheits Kategorie des Systems gemäß EN ISO 13849 1 einschließlich der Sicherheits Vorrichtung hängt auch von de...

Страница 12: ...rtemperatur 25 C 70 C Mech Lebensdauer 10 Millionen Schaltspiele Elektr Lebensdauer 100 000 Schaltspiele Verschmutzungsgrad extern 3 intern 2 Stoßspannung Uimp 4 kV Bemessungsisolationsspannung Ui 250 V Überspannungskategorie II Luft und Oberflächenabstände gemäß EN 60947 1 9 3 Stromversorgung Nennversorgungsspannung Un 24 Vac dc 50 60 Hz Art CS AT 024 120 Vac 50 60 Hz Art CS AT 120 230 Vac 50 60 ...

Отзывы: