53
type of data is indicated in the column “Max number bit/word
read/written consecutively”.
ACCESS TO BIT
CONTACT
SYM
MIN
MAX
OFFSET
READ/
WRITE
MAX NUMBER
OF BITS READ /
WRITTEN
CONSECUTIVELY
EXTERNAL
INPUT
X
0 9999
0
R
8
EXTERNAL
OUTPUT
Y
0 9999 10000 R/W
8
INTERNAL
RELAY
R
0 9999 20000 R/W
8
LINK
RELAY
L
0 9999 30000 R/W
8
TIMER
T
0 9999 40000
R
8
COUNTER
C
0 9999 50000
R
8
ACCESS TO WORD
WORD NAME
SYM
MIN
MAX
OFFSET
READ/
WRITE
MAX NUMBER
OF WORDS READ
/ WRITTEN
CONSECUTIVELY
EXTERNAL
INPUT
X
0
999
0
R
10
EXTERNAL
OUTPUT
Y
0
999 1000 R/W 10(R) / 7 (W)
INTERNAL
RELAY
R
0
999 2000 R/W 10(R) / 7 (W)
LINK
RELAY
L
0
999 3000 R/W 10(R) / 7 (W)
TIMER
T
0
999 4000
R
10
COUNTER
C
0
999 5000
R
10
INDEX
REG. X
0
0
6000 R/W
1
INDEX
REG. Y
0
0
6001 R/W
1