Document 15048  Rev. D1   07/16/97  P/N 15048:D1

5

Fire Alarm

Control Panel

Wiring

Communication between the control panel and the AFM is accomplished over a two-wire
power-limited EIA-485 serial interface (formerly referred to as RS-485). This communica-
tion, to include the wiring, is supervised by the control panel's CPU.  Loss of communication
results in "System Trouble" and "Module Failure" indications at the CPU.  Power for the AFM
must be power-limited and is provided via a separate power loop from the control panel which
is inherently supervised (loss of power also results in a communication failure at the control
panel).  No End-Of-Line Resistor needs to be installed because the EIA-485 circuit is
internally terminated on the annunciator.

Wiring Specifications

The EIA-485 circuit cannot be T-Tapped; it must be wired in a continuous fashion from the
control panel to the AFM.  The maximum wiring distance between the panel and annunciator
is 6000 feet.  The wiring size should be a 18 AWG to 14 AWG twisted-pair
cable having a Characteristic Impedance of approxi-
mately 120 ohms.  Limit the total wire resistance to 100
ohms on the EIA-485 circuit, and to 10 ohms on the power
run to the annunciator.  Do not run cable adjacent to, or in the same
conduit as, 120 volts AC service, noisy electrical circuits that are powering mechanical bells
or horns, audio circuits above 25 volts

RMS

, motor control circuits, or SCR power circuits.

Twisted-shielded wiring should be used for EIA-485 circuits that are not contained entirely
in conduit.

Functions

The fire alarm control panel automatically assigns annunciator points to the modules directly
to the right of the CPU and outward. Therefore, when installing the system modules, Initiating
Zone Modules (IZ-4, IZ-8, or IZM-8) should be installed in ribbon cable positions immediately
next to the CPU (and outward) to permit full annunciation of initiating circuits.

AFM

Annunciator

Two-wire EIA-485

Circuit

(Maximum of 6000 feet )

power-limited

Power for AFM

(18 to 14 AWG )

power-limited

www.PDF-Zoo.com

firealarmresources.com

Содержание NOTIFIER AFM-16AT

Страница 1: ...LE Installation Manual for the AFM 16AT and AFM 32A Annunciator Modules 12 Clintonville Road Northford CT 06472 203 484 7161 FAX 203 484 7118 Document 15048 07 16 97 Revision D1 ECN 97 294 www PDF Zoo com firealarmresources com ...

Страница 2: ...e unit Follow the instructions in the installation operating and pro grammingmanuals Theseinstructionsmustbefollowedtoavoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper installation Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on anoth...

Страница 3: ...s Plate Applying the Annunciator Label Installing AFM Options AFM Field Connections Installation Requirements Main Power Supply Connections Operation AFM 16AT Operation AFM 32A Operation Annunciator Point Functions Slide In Labels 4 6 8 9 9 10 12 13 13 14 15 16 17 18 18 19 20 Table of Contents Section One Section Two Section Three Section Four center www PDF Zoo com firealarmresources com ...

Страница 4: ...ontrol Relays trouble TC 2 TC 4 TCM 2 and TCM 4 circuits trouble CPU Controls Acknowledge Signal Silence and System Reset If desired the Alarm Relay Indicating Circuits 1 and 2 and the Remote Station Municipal Tie may be controlled from the AFM 16AT The AFM 32A can annunciate the following Circuits IZ 4 IZ 8 and IZM 8 Initiating Device Circuits alarm and trouble AIM 200 Software Zones alarm and tr...

Страница 5: ...nd annunciator is 6000 feet The wiring size should be a 18 AWG to 14 AWG twisted pair cable having a Characteristic Impedance of approxi mately 120 ohms Limit the total wire resistance to 100 ohms on the EIA 485 circuit and to 10 ohms on the power run to the annunciator Do not run cable adjacent to or in the same conduit as 120 volts AC service noisy electrical circuits that are powering mechanica...

Страница 6: ...le in dication of alarm and trouble conditions The AFM 16AT can be mounted in two types of backboxes the ABS 1 or ABF 1 AFM 32A H 8 3 8 W 4 3 8 D 1 3 8 The Annunciator Fixed Module 32A con tains 32 red alarm LEDs a System Trouble LED an ON LINE POWER LED and a piezo sounder with a Local Silence Acknowledge switch for audible indica tion of alarm and trouble conditions The AFM 32A can be mounted in...

Страница 7: ...rovided for use with 1 2 conduit The annun ciator mounts directly to the ABS 1 without a dress plate Note The ABS 1 will not support the installa tion of the AKS 1 or APJ 1 AKS 1 The Annunciator Key Switch provides access security for the control switches on the AFM 16AT Includes a key mounting hardware and an adhesive backed annunciator label The AKS 1 can only be employed with a flush mount type...

Страница 8: ... 1 Only Remove the backing from the Annunciator Label and affix to the dress plate as illustrated in Figure 3 6 ABF 1 Only If employing an Annunciator Key Switch AKS 1 mount the switch to the dress plate Plug the switch leads to Connector J4 on the Annunciator see Figure 3 7 ABF 1 Only If employing an Annunciator Phone Jack APJ 1 mount the jack to the ABF 1 Dress Plate Connect the telephone circui...

Страница 9: ...r circuits Twisted shielded wiring should be used for EIA 485 circuits that are not contained entirely in conduit Do not allow the shield to enter or touch the annunciator enclosure as illustrated above The shield should only be terminated at the fire alarm control panel Wire nut multiple shields together outside of the cabinet Figure 3 1 Mounting the Backbox Select a knockout on the backbox Mount...

Страница 10: ...ctions as well as alarm zones 1 through 8 Set C Custom User Labels These blank labels can be customized by the user If information is to be typed onto these labels they should be reproduced on a copy machine so that the entire page can be inserted into a typewriter Two sets of custom user labels are provided so that one set may be used as a work sheet Effective Window Size The size of the visible ...

Страница 11: ...Set E Factory printed system zone labels These provide labels for System Alarm Supervisory condi tion and alarm zones 1 through 24 Set F Custom User Labels These blank labels can be customized by the user If information is to be typed onto these labels they should be reproduced on a copy machine so that the entire page can be inserted into a typewriter Effective Window Size The size of the visible...

Страница 12: ...able the local piezo to sound during alarm trouble or supervi sory activity within the system Jumper JP1 brown Cut this jumper to display the status of the eight CPU func tions in the first eight points on the annunciator Remove the center pages of this manual If using the custom user display labels type the appropriate information on the labels Carefully cut out the labels and insert them into th...

Страница 13: ...ts and lock washers provided ABF 1 Dress Plate AFM Figure 3 6 Applying the Annunciator Label Remove backing from adhesive backed Annunciator Label and affix the label to the bottom of the ABF 1 Dress Plate as illustrated Note If an AKS 1 is to be installed use the label supplied with the appropriate kit and discard the other label www PDF Zoo com firealarmresources com ...

Страница 14: ...ug the switch leads from the AKS 1 into Connector J4 on the annunciator Telephone Circuit red wire Telephone Circuit black wire Telephone Circuit black wire Telephone Circuit red wire If employing an Annunciator Phone Jack APJ 1 mountthejacktotheABF 1Dress Plate Connect the telephone circuit to the leads of the APJ 1 as shown below www PDF Zoo com firealarmresources com ...

Страница 15: ... power wiring to the terminal blocks on the back of the AFM as illustrated below Caution Failure to observe proper polarity on these connections may result in damage to the annunciator TB2 TB1 2 1 2 1 24 VDC 24 VDC EIA 485 and power must be power limited EIA 485 EIA 485 www PDF Zoo com firealarmresources com ...

Страница 16: ...ystem 5000 ensure that the CPU U4 ROM software is Part Number 73085 or greater Figure 3 9 Connecting the EIA 485 Loop EIA 485 Supervised and Power limited Supervised and Power limited EIA 485 EIA 485 EIA 485 CPU 500 F I R E A L A R M SYSTEM 5000 AC POWER SYSTEM ALARM SUPERVISORY SIGNAL SYSTEM J11 MODULE TYPE LAMPS SWITCH 17 18 19 20 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 CPU 5000 www PDF Zoo com f...

Страница 17: ...r the AFM to MPS 24A TB3 Terminals 1 and 2 1 amp max or Terminals 3 and 4 3 amps max The total amount of current drawn from these terminals cannot exceed the above ratings in standby or in alarm 24 VDC Power to AFM TB1 Terminal 1 MPS 24A MPS 24B Main Power Supply Connect the power run for the AFM to MPS 24B TB2 Terminals 1 and 2 No more than 200 mA current can be drawn from these terminals in stan...

Страница 18: ...l latch on solid and the piezo will be silenced On Line LED This green indicator flashes during communication with the control panel System Trouble LED This yellow indicator lights for all trouble conditions in the system not just for those points or zones mapped to the annunciator Control Switch Functions as a local Lamp Test for the two LEDs dedicated to this point If not inhibited the control s...

Страница 19: ...he piezo will be silenced On Line LED This green indicator flashes during communication with the control panel System Trouble LED This yellow indicator lights for all trouble conditions in the system not just for those points or zones mapped to the annunciator Local Silence Acknowledge Switch If the Annunciator loses communication with the control panel the yellow System Trouble LED will flash 32 ...

Страница 20: ...EDs will be illuminated for a supervisory condition Illumination of the yellow LED alone indicates a trouble condition open circuit on a supervisory zone 5 3 6 3 3 4 4 4 C P U 1 M O D U L E S Yellow LED Indicates System Trouble Indicates that signals have been silenced not used Indicates Supervisory condition Indicates trouble status of circuit Indicates trouble status of circuit Indicates trouble...

Страница 21: ...Document 15048 Rev D1 07 16 97 P N 15048 D1 21 NOTES www PDF Zoo com firealarmresources com ...

Страница 22: ...Document 15048 Rev D1 07 16 97 P N 15048 D1 22 NOTES www PDF Zoo com firealarmresources com ...

Страница 23: ...Document 15048 Rev D1 07 16 97 P N 15048 D1 23 www PDF Zoo com firealarmresources com ...

Страница 24: ...e only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges thatNOTIFIER is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience transportation damage m...

Страница 25: ...ted line and insert into the right hand side of AFM 16AT ALARM ZONE 1 ALARM ZONE 2 ALARM ZONE 3 ALARM ZONE 4 ALARM ZONE 5 ALARM ZONE 6 ALARM ZONE 7 ALARM ZONE 8 ALARM ZONE 16 ALARM ZONE 15 ALARM ZONE 14 ALARM ZONE 13 ALARM ZONE 12 ALARM ZONE 11 ALARM ZONE 10 ALARM ZONE 9 Set A Zone Label 1 Cut out along dotted line and insert into the left hand side of AFM 16AT Set A Zone Label 2 LOCAL SILENCE AND...

Страница 26: ...M ZONE 3 ALARM ZONE 32 Set D Zone Label 2 Cut out along dotted line and insert into the right hand side of AFM 32A ALARM ZONE 17 ALARM ZONE 18 ALARM ZONE 31 ALARM ZONE 30 ALARM ZONE 29 ALARM ZONE 28 ALARM ZONE 27 ALARM ZONE 26 ALARM ZONE 25 ALARM ZONE 24 ALARM ZONE 23 ALARM ZONE 22 ALARM ZONE 21 ALARM ZONE 20 ALARM ZONE 19 Cut out along dotted line and insert into the left hand side of AFM 32A LOC...

Страница 27: ... along dotted line and insert into the right hand side of AFM 16AT Set C Custom User Label 1 Cut out along dotted line and insert into the left hand side of AFM 16AT Set C Custom User Label 2 LOCAL SILENCE AND ACKNOWLEDGE Cut out along dotted line and insert into the right hand side of AFM 16AT ON LINE SYSTEM TROUBLE SYSTEM TROUBLE www PDF Zoo com firealarmresources com ...

Страница 28: ...ZONE 24 Cut out along dotted line and insert into the right hand side of AFM 32A ALARM ZONE 9 ALARM ZONE 10 ALARM ZONE 23 ALARM ZONE 22 ALARM ZONE 21 ALARM ZONE 20 ALARM ZONE 19 ALARM ZONE 18 ALARM ZONE 17 ALARM ZONE 16 ALARM ZONE 15 ALARM ZONE 14 ALARM ZONE 13 ALARM ZONE 12 ALARM ZONE 11 Cut out along dotted line and insert into the right hand side of AFM 32A ON LINE Set F Custom User Label 2 Set...

Отзывы: