![Pittway NOTIFIER AFM-16AT Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/pittway/notifier-afm-16at/notifier-afm-16at_installation-manual_1560296012.webp)
Document 15048 Rev. D1 07/16/97 P/N 15048:D1
12
AKS-1 Connector
(shown here for reference
only)
Jumper JP3 (orange)
Cut this jumper to enable the Local Si-
lence/Acknowledge switch and all point
control switches (on the AFM-16AT). This
will allow the execution of system control
functions, such as ACKNOWLEDGE and
RESET, from the AFM-16AT.
Note: Jumper JP1 must also be cut to
execute these functions.
Figure 3-4: Annunciator Jumper Options
Jumper JP2 (red)
Cut this jumper to enable the local piezo to
sound during alarm, trouble, or supervi-
sory activity within the system.
Jumper JP1 (brown)
Cut this jumper to display the
status of the eight CPU func-
tions in the first eight points on
the annunciator.
Remove the center pages of this manual. If
using the custom user display labels, type
the appropriate information on the labels.
Carefully cut out the labels and insert them
into the AFM by slipping them into the label
slots on the back side of the annunciator
face plate.
Note: To ensure the best fit, cut directly
along the dotted line surrounding each
label.
Figure 3-3: Inserting Display Labels
AFM-16AT
www.PDF-Zoo.com
firealarmresources.com
Содержание NOTIFIER AFM-16AT
Страница 21: ...Document 15048 Rev D1 07 16 97 P N 15048 D1 21 NOTES www PDF Zoo com firealarmresources com ...
Страница 22: ...Document 15048 Rev D1 07 16 97 P N 15048 D1 22 NOTES www PDF Zoo com firealarmresources com ...
Страница 23: ...Document 15048 Rev D1 07 16 97 P N 15048 D1 23 www PDF Zoo com firealarmresources com ...