![Pittway NOTIFIER AFM-16AT Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/pittway/notifier-afm-16at/notifier-afm-16at_installation-manual_1560296018.webp)
Document 15048 Rev. D1 07/16/97 P/N 15048:D1
18
Section Four:
Operation
If the Annunciator loses communication with the
control panel, all the yellow LEDs will flash.
16 Annunciator Points
Acknowledge
Switch
This switch serves two purposes:
1) When pressed, it lights all the LEDs on the AFM
(except the On Line LED) and sounds the piezo for
as long as the switch is held down.
2) It acknowledges all status changes for the AFM.
Flashing LEDs will latch on solid and the piezo will
be silenced.
On Line LED
This green indicator flashes during communication
with the control panel.
System Trouble LED
This yellow indicator lights for all trouble conditions
in the system (not just for those points or zones
mapped to the annunciator).
Control Switch
Functions as a local Lamp Test for the two
LEDs dedicated to this point.
If not inhibited, the control switches can
also be used to execute the system func-
tions of ACKNOWLEDGE, SIGNAL SI-
LENCE, and SYSTEM RESET, and con-
trol system outputs (see Table 4-1).
Red LED
Yellow LED
Figure 4-1: AFM-16AT Operation
www.PDF-Zoo.com
firealarmresources.com
Содержание NOTIFIER AFM-16AT
Страница 21: ...Document 15048 Rev D1 07 16 97 P N 15048 D1 21 NOTES www PDF Zoo com firealarmresources com ...
Страница 22: ...Document 15048 Rev D1 07 16 97 P N 15048 D1 22 NOTES www PDF Zoo com firealarmresources com ...
Страница 23: ...Document 15048 Rev D1 07 16 97 P N 15048 D1 23 www PDF Zoo com firealarmresources com ...