52
PLAYA - USE AND MAINTENANCE
ANTI STAGNATION FUNCTION (AUTOMATIC)
It is an automatic function that activates the blower for 30 seconds and the filter
pump for 3 hours when the latter has been off for more than 48 hours.
MINIMUM TEMPERATURE FUNCTION (AUTOMATIC)
It allows you to prevent the water from cooling to ambient temperature, thus
minimizing the energy consumption and the time to bring the temperature of use.
It is automatically activated when the “water heating” function is turned off. It is
to regulate the temperature with the same function mode “Heating water using the
reference temperature = 10 °C”. For the hysteresis, use the fixed value of 1 ° C.
ALARM SIGNALS
The following table summarizes all the signal codes of alarms, with their
descriptions, that the control unit is capable of signaling.
DISPLAYED
MESSAGE
ACTIONS TAKEN
FROM THE
CONTROL SYSTEM
ITEM THAT
GENERATED THE
ALARM
POSSIBLE
CAUSES
RECOVERY MODE
no alarm, but
the controller’s
display does
not turn on
--
--
lack of power.
Fuse of the
controller
interrupted
check the power
supply line. Check
the fuse of the
control unit
FLOW
filter pump
turned off,
heater switched
off if turned on
the flow switch
has detected
insufficient
flow
clogging of the
suction circuit
(prefilter
basket clogged,
clogged filter,
any foreign
body in the
pump impeller)
after removing the
cause, the alarm is
reset by pressing
the button “Filter
pump”
and then the
“hand” button
if, prior to the
alarm, the heater
was turned on,
the reset is active
again after 3
minutes.
Содержание PLAYA 1
Страница 2: ...2 PLAYA USO E MANUTENZIONE ...
Страница 3: ...3 PLAYA USO E MANUTENZIONE GENERAL INDEX pag 4 pag 34 pag 60 pag 86 pag 112 17 GIU ...
Страница 137: ...137 PLAYA USO E MANUTENZIONE NOTE ...
Страница 138: ...138 PLAYA USO E MANUTENZIONE NOTE ...
Страница 139: ...139 PLAYA USO E MANUTENZIONE NOTE ...
Страница 140: ...140 PLAYA USO E MANUTENZIONE NOTE ...
Страница 144: ...GARANZIA ITALIA ...