37
I3HEAT
I2HEAT
I1HEAT
Off
Decrease
Hold
Resume
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
Note:
When AC is in “hold” zone for 3 minutes, the compressor frequency will rise to the higher level. (The
frequency will increase twice at most)
8.4.3.2 Outdoor fan running rules:
17
15
Low
High