9.4.4 Fan speed has been out of control diagnosis and solution(E3)
Error Code
E3
Malfunction decision
conditions
When indoor fan speed stays too low (<300RPM) for certain time,
the unit will stop and the LED will display the failure.
Supposed causes
●
Wiring mistake
●
Fan assembly fault (check for rubbing/misalignment)
●
Fan motor faulty
●
PCB faulty
Trouble shooting: