34
For 18k, 24k models:
Compressor
on
off
on
on
on
off
off
off
4-way valve
Outdoor fan
Indoor fan
Indoor fan breeze(10s)
xx
no longer than 10m
Frequency F8
30s
10s
10s
Frequency F2
XX=60 for 18k model, XX=90 for 24k model.
8.4.3.5 Evaporator coil temperature
protection
----T2> TEH2
℃
, the compressor running
frequency decreases to the lower level and
runs for 20s.
When the frequency decreases to F2 and the
T2 is still over TEH2
℃
for 3 minutes, the
compressor will stop.
----T2<48
℃
or T2 stays in 48
℃
~ TEH2
℃
for 6
minutes, the frequency will not be limited by T2.
----T2>60
℃
, the compressor will stop and
restart when T2<48
℃
.
8.4.4 Auto-mode
This mode can be chosen with remote
controller and the setting temperature can be
changed between 17~30
℃
.
In auto mode, the machine will choose cooling,
heating or fan-only mode according to ΔT (ΔT
=T1-Ts).
ΔT=T1-Ts
Running mode
ΔT
>
1
℃
Cooling
-1<ΔT≤1
℃
Fan-only
ΔT≤-1
℃
Heating
Indoor fan will run at auto fan of the relevant
mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating
and cooling, the compressor will stop for 15
minutes and then choose mode according to
T1-Ts.
If the setting temperature is modified, the
machine will re-determine the running function
again.
8.4.5 Drying mode
8.4.5.1 Indoor fan speed is fixed at breeze
speed and can’t be changed. The louver angle
is the same as in cooling mode.
8.4.5.2 Compressor running rules
2.0
1.5
1.0
F3
F2
F1
F1
2.5
0.5
0.0
8.4.5.3 Low indoor room temperature protection
In drying mode, if room temperature is lower
than 10
℃
, the compressor will stop and not
resume until room temperature exceeds 12
℃
.
8.4.5.4 Evaporator anti-freezing protection,
condenser high temperature protection and
outdoor unit frequency limit are active and the
same as that in cooling mode.
8.4.5.5 The outdoor fan operates the same as
in cooling mode.
8.4.6 Forced operation function
8.4.6.1 Enter forced operation function:
When the machine is off, pressing the
EMERGENCY touch button will switch the unit
into forced auto mode. While in Auto Mode,
pressing and holding the button once again
within 5 seconds, will switch the unit into forced
cooling mode. In forced auto, forced cooling or
any other operation mode, pressing touch
button will turn off the system.
Содержание WAE009AMFI15RL
Страница 7: ...5 2 2 Part names of Indoor Outdoor units ...
Страница 16: ...14 5 Wiring Diagram 5 1 Indoor Unit 9000 BTU 230V Heat Pump 12000 BTU 230V Cool Only 12000 BTU 230V Heat Pump ...
Страница 18: ...16 24000 BTU 230V Cool Only 24000 BTU 230V Heat Pump ...
Страница 20: ...18 18000 BTU 230V Cool Only 18000 BTU 230V Heat Pump 24000 BTU 230V Cool Only 24000 BTU 230V Heat Pump ...
Страница 22: ...20 For 18000 BTU 230V Cool Only 18000 BTU 230V Heat Pump For 24000 BTU 230V Cool Only 24000 BTU 230V Heat Pump ...
Страница 53: ...51 P U P V ...
Страница 54: ...52 P W P N ...